Page 14
9PX 1-3 KVA US_EN
2. Presentation
Submenu
Available settings
Default settings
In/Out settings
Output voltage
[100V] [110V] [120V] [125V]
[200V] [208V] [220V] [230V] [240V]
[120V]
[208V]
Output frequency
Mode: [Normal] [Converter] [Marine]
Frequency can be changed in
Frequency [Converter] mode
In [Marine] mode output frequency
follows input frequency
[Normal]
Output mode
Mode: [Industrial] [IT] [Custom]
Overload: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
Short-circuit: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
[IT]
[Inv>BP>Inv]
[Inv>Stop]
Input volt hysteresis Sets input voltage hysteresis
from [1] to |10V]
[10V]
High Efficiency
mode
[Enabled] [Disabled]
Power the output from Bypass for high
efficiency
[Disabled]
Bypass settings
[Volt low]
[Volt high]
[Qualify]
[Hz synch]
[Unsynch]
[80V] LV; [160V] HV;
[144V] LV; [276V] HV;
[In spec];
[5%];
[Half cycle]
Load segments
[Auto start delay]
[Auto shutdown delay]
UPS: [0s]; Group1: [3s];
Group2: [6s]
UPS: [Disabled];
Group1: [Disabled];
Group2: [Disabled]
Overload
prealarm
[10%] … [102%]
Load % when overload alarm occurs
[102%]
On/Off settings
Start/Restart
[Cold start] [Auto restart] [Auto start]
[Start on bypass]
[Cold start] [Auto restart] are
Enabled
[Auto start] [Start on bypass]
are Disabled
Forced reboot
[Enabled] [Disabled]
[Timer] [10s] … [180s]
When mains recover during a
shutdown sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown sequence
will not complete, UPS stays on.
[Enabled]
[10s]
Energy saving
[Enabled] [Disabled]
[Timer] [1min] … [15min]
[Level] [100W] … [1000W]
If Enabled, UPS will shut-down after
defined duration. of back-up time, if
load is less than set value.
[Disabled]
[5min]
[100W]
Sleep mode
[Enabled] [Disabled]
[Timer] [10min] … [120min]
If Disabled, LCD and communication
will turn OFF immediately after UPS is
OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled]
[90min]
Site wiring fault
[Enabled] [Disabled]
Prevents from starting the UPS in case
of phase vs neutral wires swapping.
[Disabled]
Power Off alert
[Enabled] [Disabled]
If Enabled, activates a confirmation
screen that requires user confirmation
after pressing the power button,
before the UPS shutdown occurs.
[Enabled]