Page 27
9PX 1-3 KVA US_EN
ENGLISH
3. Installation
9PX 2200GRT & 9PX 3000GRT
1
MBP
LOAD
29
30
33
31
34
35
36
15
28
32
6
7
5
1.
Connect the input
36
on the
HotSwap MBP
module to the
AC-power source.
2.
Connect the UPS input cable
1
to
the “UPS Input socket”
35
on the
HotSwap MBP
module.
3.
Connect the UPS outlet
5
to the
“UPS Output”
34
on the HotSwap
MBP module (using the cable
28
supplied for G models).
These cables and the connectors
are marked in red.
4.
Connect the equipment to the
outlets
29
on the
HotSwap MBP
module. These outlets differ,
depending on the version of the
HotSwap MBP
module.
Caution: when using HotSwap
MBP, do not use UPS outlets to
directly power equipment. As
operating the bypass switch
33
will cut supply voltage to the
equipment.
HotSwap MBP module operation
32
33
31
UPS start-up with the HotSwap MBP module
1.
Check that the UPS is correctly connected to the
HotSwap MBP
module.
2.
Set switch
33
to Normal position.
3.
Start the UPS by pressing the ON/OFF button on the UPS control panel.
The load is supplied by the UPS.
LED
31
"UPS ON - OK to switch" on the
HotSwap MBP
module goes ON.
HotSwap MBP module test
1.
Set switch
33
to Bypass position and check that the load is still supplied.
2.
Set switch
33
back to Normal position.
The HotSwap MBP module has a rotary
switch
33
with two positions:
Normal
the load is supplied by the UPS,
LED
31
is on.
Bypass
the load is supplied directly by
the AC-power source. LED
32
is on.