Page 44
9PX 1-3 KVA US_EN
Table 8. Environmental and safety
Certifications
IEC/EN 62040-1
IEC/EN 62040-2 : Cat. C1
IEC/EN 62040-3
UL1778 5th edition
CSA 22.2
EMC (Emissions)*
CISPR22 Class B
FCC part 15 Class B / ICES-003
EMC (Immunity)
IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV Air Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): Power (Coupling network) 4 kV / Ethernet (Coupling
clamp) 2 kV
IEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV Common Mode /
1 kV Ethernet
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
*
for output cable < 10m.
Agency markings*
CE / cULus / NOM / Energy Star / BSMI
Operating temperature
0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note:
thermal protection switches load to Bypass in case of overheating.
Storage temperature
0 to 40°C (32 to 104°F) with batteries
-25 to 55°C (-13 to 130°F) without batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity
0 to 96% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level, no derating for 35°c (95°F)
room temperature
Transit altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible noise
< 47 dBA at 1 meter typical for 2K et 3K models
< 40 dBA at 1 meter typical for 70, 1K et 1K5 models
*
9PX1000GRT, 9PX 1500GRT, 9PX2200GRT, 9PX3000GRT, 9PX3000GLRT have CE/ cULus/Energy Star/
BSMI.
9PXEBM36RT, 9PXEBM48RT, 9PXEBM72RT have CE / cULus / NOM.
Table 9. Battery
Internal batteries
EBM
Rack / Tower
configuration
700VA: 36Vdc - 3 x 12V, 9Ah
1000VA LV: 36Vdc - 3 x 12V, 9Ah
1000VA HV :48Vdc - 4 x 12V, 7Ah
1500VA: 48Vdc - 4 x 12V, 9Ah
2200VA: 72Vdc - 6 x 12V, 7Ah
3000VA: 72Vdc - 6 x 12V, 9Ah
9PXEBM36RT: 36Vdc - 2 x 3 x 12V, 7Ah
9PXEBM48RT: 48Vdc - 2 x 4 x 12V, 9Ah
9PXEBM72RT: 72Vdc - 2 x 6 x 12V, 9Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25°C (77°F). Lifetime is reduced above 25°C (77°F).
Monitoring
Advanced monitoring for earlier failure detection and warning
EBM battery cable
length
350 mm / 13.78 in
8. Specifications