Page 13
9PX 1-3 KVA US_EN
ENGLISH
2.6 Display functions
Press the Enter (
) button to activate the menu options. Use the two middle buttons ( and ) to scroll
through the menu structure. Press the Enter (
) button to select an option. Press the
button to cancel
or return to the previous menu.
Main menu
Submenu
Display information or Menu function
Measurements
[Load] W VA A pf / [Input/Output] V Hz / [Efficiency] % /
[Battery] % min V n° EBM / [Battery remaining life] months /
[Average power usage] Wh / [Cumulated power] Wh
Control
Go to Bypass
Transfers the UPS on Bypass mode
Load segments On/Off
Commands the load segments
Start battery test
Starts a manual battery test
Connectivity test
Tests dry contact relay outputs and relay card contacts.
Simulates line failure and battery low
Function reset
Clears active fault, power usage, battery remaining life, reset
NMC, Restore factory settings.
Settings
Local settings
Sets product general parameters
In/Out settings
Sets Input and Output parameters
On/Off settings
Sets On/Off conditions
Battery settings
Sets battery configuration
Com settings
Sets communication parameters
Event log
Event filter
Selects faults, alarms and/or events to display
Event list
Displays the events stored
Reset event list
Clears events
Fault log
Fault list
Displays the faults stored
Reset fault list
Clears faults
Identification
[Product type/model] / [Part/Serial number] / [UPS/NMC firm-
ware] / [Com card IPv4], [Com card IPv6], [Com card MAC]
Registration
Links to Eaton registration website
2.7 User settings
The following table displays the options that can be changed by the user.
Submenu
Available settings
Default settings
Local settings
Language
[English] [Français] [Deutsch] [Español]
[
Русский
] [Português] [Italiano]
[Simplified Chinese] [Japanese]
Menus, status, notices and alarms,
UPS fault, Event Log data and settings
are in all supported languages.
[English]
User selectable when UPS is
powered for the first time.
Date/ time
Format:
[International] [US]
[US]
LCD
Modify LCD screen brightness and
contrast to be adapted to room light
conditions.
Audible alarm
Mode:
[Enabled] [Disabled on battery]
[Always disabled] Enable or disable the
buzzer if an alarm occurs.
[Enabled]
Level: [High] [Low]
[High]
Protected access
[Enabled] [Disabled]
Password is: 0577
[Disabled]