Page 15
9PX 1-3 KVA US_EN
ENGLISH
Submenu
Available settings
Default settings
Battery settings
Automatic battery
test
In ABM cycling mode :
[No test] [Every ABM cycle]
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
[Every ABM cycle]
[Every week]
Low battery
warning
[Capacity] [0%] … [100%]
[Runtime] [0min] … [60min]
The alarm triggers when the set
percentage of battery capacity or
remaining back-up time is reached.
[0%]
[3min]
Restart bat. level
[0%] ... [100%]
If set, automatic restart will occur only
when percentage of battery charge is
reached.
[0%]
Battery charge
mode
[ABM cycling] [Constant charge]
[ABM cycling]
External battery
[Auto detection] [Manual EBM set.]
[Manual battery set.]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
Deep Disch.
protect.
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Warranty void if set to No.
[Yes]
Com settings
Input signals
[ROO] [RPO] [DB9-4]
Sets Input signals parameters
(function, delay, operation) through
external contact connectors or RS232
port.
ROO port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s]
- [Active]: [Open] [Closed]
RPO port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s]
- [Active]: [Open] [Closed]
DB9-4 port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s]
- [Active]: [High] [Low]:
[No]
[0s]
[Closed]
[No]
[0s]
[Open]
[No]
[0s]
[High]
2. Presentation
Summary of Contents for 9PX 700 RT
Page 46: ...Page 46 9PX 1 3 KVA US_EN...