2.3 Firmware upgrade
Check that UPS firmware version is parallel compatible:
Screen menu
Identification
UPS/NMC firmware.
If
“// Ready”
doesn’t appear just next to the UPS firmware number, that means the UPS cannot be
connected in parallel.
Contact your Eaton reseller to download the latest firmware.
2.4 Parallel UPS screen
1
Press button of any one of the two
UPS to start the parallel system.
2
The Power display is the UPS power and
not the load power. The load power is
the sum of UPS1 power d UPS2
power display
3
"1UPS + 1UPS redundant"
means the
load power is less than the maximum
power of one UPS.
"2UPS + 0UPS redundant"
means the
load power is more than the maximum
power of one UPS.
"1UPS + 0UPS redundant"
means only
one UPS powers the load.
2.5 Parallel setting
Press the Enter (
) button to activate the menu options.
Main menu
Submenu
Available settings
Settings
In/Out settings
Redundancy mode
[Parallel Operation]
[Redundancy Only]
[Parallel Operation]:
set this mode to cancel the audible alarm when the load power is more than the
maximum power of one UPS: "Parallel Operation" is the default mode.
[Redundancy Only]:
set this mode to have an audible alarm when the load power is more than the
maximum power of one UPS.
Summary of Contents for 9PX 8000i RT6U HotSwap Netpack
Page 2: ...9PXMEZ6Ki 9PXMEZ11Ki Installation and user manual English Fran ais Deutsch Espa ol...
Page 3: ......
Page 100: ...ModularEasy 9PXMEZ6Ki 9PXMEZ11Ki Copyright 2014 EATON 614 09354 01_RU...
Page 102: ...3 614 09354 01_RU ModularEasy 15 C 60 C ModularEasy EATON Eaton ModularEasy...
Page 107: ...8 614 09354 01_RU 2 2 3 UPS NMC Ready Eaton 2 4 1 2 Power 1 2 3 1 1 2 0 1 0 2 5 Enter...
Page 109: ...10 614 09354 01_RU 3 3 4 3 5 9RK...
Page 110: ...11 614 09354 01_RU 3 3 6 19 EBM 9PX EBM 240V 3 7 Trollet Frame BINTSYS 9PXMEZ11Ki 9PXMEZ6Ki...
Page 114: ...15 614 09354 01_RU 4 10 1 ModularEasy 11 9PX...
Page 124: ......
Page 125: ...www eaton com Powerquality EATON 9PX_ModularEasy 614 09354 01...