7. UPS maintenance
7.5
Replacing the UPS equipped with a HotSwap MBP
The HotSwap MBP allows to service or replace the UPS without interrupting the connected loads.
Refer to the specific user manual for more information about HotSwap MBP.
To remove the UPS:
1.
Press any button to activate the menu options. Select Control then Go to Bypass.
2.
Check that the UPS is in Bypass mode (Bypass LED should be On).
3.
Turn the HotSwap MBP switch to the Bypass position : the red LED on the HotSwap MBP goes On,
indicating that the load is now powered directly from utility power.
4.
Set the Normal AC source and Bypass AC source switches on the HotSwap MBP to the "O" position
and wait for 30s.
5.
The UPS stops and can now be disconnected.
To reinstall the UPS:
1.
Check that the UPS is correctly connected to the HotSwap MBP.
2.
Set the Normal AC source and Bypass AC source switches on the HotSwap MBP to the "I" position.
3.
Press the button to switch On the UPS.
4.
Select Control then Go to Bypass.
5.
Turn the HotSwap MBP switch to the Normal position: the red LED on the HotSwap MBP goes Off,
indicating that the load is now powered by the UPS (Bypass LED should be On).
6.
Select Control then Go back normal.
7.
Check that the UPS is in Online mode: the load is now protected by the UPS (Online LED should be On).
7.6
Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of
z
batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
z
eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.
Summary of Contents for 9PX EBM 240V