Page 43
8-11kVA EU_EN
ENGLISH
9. Specifications
Agency markings
CE / C-Tick / cULus
Operating temperature
0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note:
thermal protection switches load to Bypass in case of overheating.
Storage temperature
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity
0 to 95% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible noise
< 48 dBA at 1 meter typical for 8kVA models
< 50 dBA at 1 meter typical for 11kVA models
Table 9. Battery
EBMs
Rack / Tower
configuration
9SXEBM240: 240Vdc 20 x 12V, 7Ah
9PXEBM240: 240Vdc 20 x 12V, 9Ah
Fuses
63A for 8kVA models
80A for 11kVA models and EBM
Type
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F)
Monitoring
Advanced monitoring for earlier failure detection and warning
Battery port
External three-pole SBS75G White connector on Power Module for connection
to EBM
EBM battery
cable length
40cm (15.7in)
Table 10. Communication options
Communication bay
(1) available independent communication bay for connectivity cards
Compatible connectivity
cards
Network-MS
Modbus-MS
Relay-MS
Communication ports
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Parallel port (DB15): only for 9PX models
Relay output contacts
(4) programmable relay outputs (normally open or normally closed)
Remote On/Off
2 pins jumper (normally open)
Remote Power Off
3 pins jumper (normally open or normally closed)
Summary of Contents for 9PX EBM 240V