Eaton 9PX Lithium-Ion
P-164001006—Rev 01
43
Table 12. Electrical Output (Continued)
All Models
Normal Mode
Efficiency Mode
Battery Mode
Frequency Regulation
Sync with line ±5% of nominal line frequency (outside this
range: ±0.5% of auto-selected nominal frequency)
±0.5% of auto-selected
nominal frequency
Nominal Output
[100V] [110V] [120V] [125V]
[200V] [208V] [220V] [230V] [240V] (G models)
Frequency
50 or 60 Hz, autosensing or configurable as a frequency converter
Output Overload
Online mode:
102%~130% :12s
130%~150% :2s
>150% :shutdown after 300ms
Percent is based on nominal Watt/VA.
Transfer behavior can change (see output mode setting on page 14)
Battery mode:
102%~130% :12s
>130% :2s
Overload warning then transfer to stop output
Output Overload ( Bypass
Mode )
102%~110% :Overload warning
110%~130% :shutdown after 5mins
130%~150% :shutdown after 15s
>150% :shutdown after 300ms
Percent is based on nominal current in bypass mode
Voltage Waveform
Sinewave
Harmonic Distortion
< 3% THDV on linear load
< 5% THDV on non-linear load
Transfer Time
Online Mode: 0ms
High Efficiency mode: 10ms maximum (due to loss of utility)
Power Factor
Up to 0.9
Load Crest Ratio
Up to 3:1
Table 13. Electrical Output Connections
Model
Output Connection
Output Cable
9PX1500RT-L
5-15R (2)
No
9PX2000RT-L
5-20R(2) + L5-20R(1)
5-20R(2) Group1
5-20R(2) Group2
No
9PX3000RT-L
5-20R(2) + L5-30R(1)
5-20R(2) Group1
5-20R(2) Group2
No
9PX1500GRT-L
(4) IEC10A
(2) IEC10A
(2) IEC10A (2) IEC 10A
No