Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 03

37

C

Chhaapptteerr 77 TTrroouubblleesshhoooottiinngg

77..11

TTyyppiiccaall A

Allaarrm

mss aanndd FFaauullttss

The Eaton 9PX are designed for durable, automatic operation and also alert you whenever potential operating problems may
occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are
preventive alarms intended to alert the user.

Events are silent status information that are recorded into the Event log. Example = "AC freq in range".

Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking.
Some alarms may be announced by a beep every 3 seconds. Example = "Battery low".

Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on the
LCD with a specific message box. Example = Out. short circuit.

Use the following troubleshooting chart to determine the UPS alarm condition.

Checking the Alarms and Faults

To check the Event log or Fault log :

1.

Press any button on the front panel display to activate the menu options.

2.

Press the button to select Event log or Fault log.

3.

Scroll through the listed events or faults.

The following table describes typical conditions.

Conditions

Possible cause

Action

Battery mode

LED is On.
1 beep every 10 seconds

A utility failure has occurred and the UPS
is in battery mode.

The UPS is powering the equipment with
battery power. Prepare your equipment
for shutdown.

Battery mode

LED is On.
1 beep every 3 seconds

The UPS is in Battery mode and the
battery is running low.

This warning is approximate, and the
actual time to shutdown may vary
significantly. Depending on the UPS load
and number of Extended Battery Modules
(EBMs), the "Battery Low" warning may
occur before the batteries reach 20%
capacity.

No battery

LED is On
Beep continuous

The batteries are disconnected.

Verify that all batteries are properly
connected. To clear a battery
disconnected alarm a battery test must
be initiated. See

Table 5

If the condition

persists, contact your service
representative.

Battery fault

LED is On
Beep continuous

The battery test is failed due to bad or
disconnected batteries.

Verify that all batteries are properly
connected. If the condition persists,
contact your service representative. To
clear a battery disconnected alarm a
battery test must be initiated. See

Table 5

If the condition persists, contact

your service representative.

Summary of Contents for 9PX1000IRT2U-L

Page 1: ...p n P 164001006 Revision 03 9PX1500IRT2U L 9PX1000IRT2U L 9PX2200IRT2U L 9PX3000IRT2U L 9PXEBM48RT1U L 9PXEBM72RT1U L Advanced Users Guide Eaton 9PX Lithium Ion...

Page 2: ...dance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the use...

Page 3: ...ctrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supp...

Page 4: ...age temperature less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of elem...

Page 5: ...ion 16 3 5 Connecting the EBM s 16 3 6 Detecting other Accessories 18 3 7 UPS Connection without Hotswap MBP Module 19 3 8 Connection with a Hotswap MBP Module Optional Accessory 20 4 4 C Co om mm mu...

Page 6: ...a Hotswap MBP 35 6 5 Recycling The Used Equipment 35 7 7 T Tr ro ou ub blle es sh ho oo ot tiin ng g 3 37 7 7 1 Typical Alarms and Faults 37 7 2 Silencing the Alarm 38 7 3 Service and Support 38 7 4 C...

Page 7: ...ET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulations for the disposal of packing materi...

Page 8: ...ality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With th...

Page 9: ...D H W Table 2 Weights and Dimensions Model Dimensions D x W x H mm inch Weight kg lb 9PX1000IRT2U L 450 x 440 x 86 5 17 7 x 17 3 x 3 4 15 6 34 3 9PX1500IRT2U L 450 x 440 x 86 5 17 7 x 17 3 x 3 4 15 8...

Page 10: ...ry group outlets for connection of critical equipment 6 Group 1 programmable outlets for connection of equipment 7 Group 2 programmable outlets for connection of equipment 8 Connector for automatic re...

Page 11: ...Relay Card BINTSYS Battery Integration System MBP3KI MBP3KIF MBP3KID MBP3KIH MBP3KIB Maintenance Bypass 2 2 4 4 C Co on nt tr ro oll P Pa an ne ell The UPS has a five button graphical LCD It provides...

Page 12: ...d equipment status Online mode 100 19min 1EBM 100 2 4kW 3 0kVA Efficiency 94 Battery status Efficiency and load group information The following table describes the status information provided by the U...

Page 13: ...not protected by the UPS 2 2 6 6 D Diis sp plla ay y F Fu un nc ct tiio on ns s Press the button to activate the menu options use the two middle buttons and to scroll through the menu structure Press...

Page 14: ...g table displays the options that can be changed by the user Table 6 User Settings Submenu Available Settings Default Settings Local Settings Language English Fran ais Deutsch Espa ol Portugu s Italia...

Page 15: ...up2 6s Auto shutdown delay UPS Disabled Group1 Disabled Group2 Disabled Overload prealarm 10 102 Load when overload alarm occurs 102 On Off Settings Start Restart Cold start Auto restart Auto start Co...

Page 16: ...attery Settings Low battery warning Capacity 0 100 0 Runtime 0min 60min 3min The alarm triggers when the set percentage of battery capacity or remaining back up time is reached Restart bat level 0 100...

Page 17: ...alarm DB9 7 UPS OK DB9 8 On bat Low bat Bat fault Bypass UPS OK Load protected Load powered General alarm Ext charger ON OVL pre alarm DB9 8 On bat Remote command Enabled Disabled If Enabled shutdown...

Page 18: ...006 Rev 03 Table 6 User Settings Continued Submenu Available Settings Default Settings On bypass UPS OK Load protected Load powered Ext charger ON Defines which event or fault generate a general alarm...

Page 19: ...the batteries were never recharged do not use the UPS Contact your service representative 3 3 2 2 C Ch he ec ck kiin ng g t th he e A Ac cc ce es ss so or ry y K Kiit t 14 21 22 23 24 16 15 19 26 27...

Page 20: ...M with a new UPS at the same time NOTE 2 Use the UPS user s guide to install both the UPS and the EBM Remember If you ordered other UPS accessories refer to specific user manuals to check the packing...

Page 21: ...Eaton 9PX Lithium Ion User Guide P 164001006 Rev 03 15 Adjustment of the orientation of the LCD panel and of the logo Adjustment of the angle of vision of the LCD panel Tower Installation...

Page 22: ...h he e E EB BM M s s A small amount of arching may occur when connecting an EBM to the UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector quickly and fi...

Page 23: ...ery Comm Battery Comm Battery Comm EBM Communications wiring UPS EBM 1 EBM 2 EBM 3 EBM 4 NOTE The EBM communication wiring connections are directional and must be connected in the correct sequence to...

Page 24: ...EBM communication wiring connections are directional and must be connected in the correct sequence to ensure proper detection regulation and lifecycle monitoring of the integrated battery management s...

Page 25: ...connect the priority loads to the outlets marked 5 and the non priority loads to the outlets marked 6 7 that can be programmed For the 9PX 2200I 3000I models connect any high power devices to the 16...

Page 26: ...ets differ depending on the version of the HotSwap MBP module Caution Do not use UPS outlets to supply equipment because use of switch 33 on the HotSwap MBP module would cut supply to the equipment An...

Page 27: ...tware Installation of the communication cards 2 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 2 secured by screws 2 Insert the communication ca...

Page 28: ...rt parameter see Settings Com Settings Shutdown commands on page 16 the unit may startup automatically IMPORTANT Warning Signal inputs have no function by default please choose a function through the...

Page 29: ...Connector type Terminal 14 AWG maximum wires External breaker specification 60 V DC 30V AC 20mA max RPO 11 ROO Remote Control Connection and Test 1 Check the UPS is shut down and the electrical suppl...

Page 30: ...l alarm Choose events that will trigger this alarm trough the LCD Settings Com settings General alarm for more information on possible events please look at page 16 Ext charger ON Control an optional...

Page 31: ...Software suite is available from eaton com download Eaton Software suite provides up to date graphics of UPS power and system data and power flow It also gives you a complete record of critical power...

Page 32: ...26 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 03 UPS Remote Control Functions...

Page 33: ...Cold start setting in ON OFF Settings in Table 6 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting...

Page 34: ...ble and your equipment is not protected however the utility power continues to be passively filtered by the UPS The indicator illuminates Depending on overload conditions the UPS remains in Bypass mod...

Page 35: ...Low Limit and Bypass Voltage High Limit settings Bypass frequency is within nominal frequency 5 You can prohibit Bypass Never or always allow Bypass with no specification checking Always For Always on...

Page 36: ...en select Event log 2 Scroll through the listed events 5 5 1 10 0 R Re et tr riie ev viin ng g t th he e F Fa au ullt t L Lo og g To retrieve the Fault log through the display 1 Press any button to ac...

Page 37: ...rical shock or burn from high short circuit current Observe the following precautions 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts...

Page 38: ...port the battery pack See Recycling the used equipment on page 38 for proper disposal 7 Verify that the replacement batteries have the same rating as the batteries being replaced 8 Put the new battery...

Page 39: ...ttery Settings Reset 7 If the UPS was shut down during the battery replacement process see 6 6 3 3 B Ba at tt te er ry y S Se et tt tiin ng gs s R Re es se et t After replacement of the internal UPS b...

Page 40: ...wering down the UPS 1 Check the UPS front panel display for active alarms or notices Resolve any active alarms before continuing See section 7 1 Typical Alarms and Faults If the indicator is on do not...

Page 41: ...ap MBP module goes ON otherwise there is a connection error between the HotSwap MBP module and the UPS 3 Set switch 33 to Normal position The red LED on the HotSwap MBP module goes OFF 1 HotSwap MBP L...

Page 42: ...36 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 03 Recycling The Used Equipment...

Page 43: ...ns 2 Press the button to select Event log or Fault log 3 Scroll through the listed events or faults The following table describes typical conditions Conditions Possible cause Action Battery mode LED i...

Page 44: ...If the UPS transferred to Bypass mode the UPS will return to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove...

Page 45: ...lp Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units...

Page 46: ...40 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 03 CE Compliance Contact...

Page 47: ...00W Table 8 Extended Battery Module List Model Configuration Battery Voltage For Power Module 9PXEBM48RT1U L Rack Tower 48Vdc 1000 1500VA 9PXEBM72RT1U L Rack Tower 72Vdc 2200 3000VA Table 9 Weights an...

Page 48: ...ut Connections Model Input Connection Input cable 9PX1000IRT2U L IEC C14 IEC10A Not Included 9PX1500IRT2U L IEC C14 IEC10A Not Included 9PX2200IRT2U L IEC C20 IEC16A 9PX3000IRT2U L IEC C20 IEC16A Tabl...

Page 49: ...s of utility Power Factor Up to 1 0 Load Crest Ratio Up to 3 1 Table 13 Electrical Output Connections Model Output Connection Output Cable 9PX1000IRT2U L 9PX1500IRT2U L 4 IEC10A 2 IEC10A group 1 2 IEC...

Page 50: ...ature 25 to 55 C 13 to 130 F Relative Humidity 0 to 96 no condensing Operating Altitude Up to 3 000 meters 9 843 ft above sea level no derating for 35 c 95 F room temperature Transit Altitude Up to 10...

Page 51: ...Eaton 9PX Lithium Ion User Guide P 164001006 Rev 03 45 Model Specifications...

Page 52: ...P 16400100603 P 164001006 03...

Reviews: