background image

Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02

37

1.

Unplug the EBM power cable and battery detection cable from the UPS. If additional EBM(s) are installed,
unplug the EBM power cable and battery detection cable from each EBM.

2.

Replace the EBM(s). See "Recycling the used equipment" for proper disposal.

A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm
personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.

3.

Plug the EBM cable(s) into the battery connector(s). Up to four EBMs may be connected to the UPS.

4.

Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.

5.

Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).

6.

Continue to the

6.3

Battery Settings Reset

.

7.

If the UPS was shut down during the battery replacement process see

5.1

Start-up and Normal Operation

.

66..33

B

Baatttteerryy S

Seettttiinnggss R

Reesseett

After replacement of the internal UPS batteries and extended battery modules the BMS auto setup and battery
life settings will need to be reset in the “

Control

” menu of the display.

1.

Reset the BMS auto setup function in the “Functions Reset” option of the control menu.

Figure 12. BMS Auto Setup Reset

UPS firmware

Control

Go to bypass
Load segments
UPS firmware
Connectivity test

Functions reset

Measurements

Control

Settings
Event log
Fault log
Identification
Register product

        Menu

100 %

   100 %

Online mode

Press the Enter Button

 to advance the menu

Functions reset

Reset Fault state
Reset power usage

BMS auto setup

Reset battery life
NMC card reset

2.4kW
3.0kVA

19min

1 EBM

Efficiency: 94%

BMS auto setup

Yes

No

Are you sure?

BMS auto setup

Done

2.

Reset the battery life counter in the “Functions Reset” option of the control menu.

Battery Settings Reset

Summary of Contents for 9PX2000RT-L

Page 1: ...p n P 164001006 Revision 02 9PX1500RT L 9PX2000RT L 9PX3000RT L 9PX1500GRT L 9PX2200GRT L 9PX3000GRT L 9PXEBM48RT L 9PXEBM72RT L Advanced Users Guide Eaton 9PX Lithium Ion ...

Page 2: ...rdance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense S Sp pe ec ciia all S Sy ym mb bo olls s The following are examples of symbols used on the product to alert you to important informat...

Page 3: ...ectrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit P Pr ro od du uc ct t S Sa af fe et ty y To connect the UPS instructions and operation described in the manual must be followed in the indicated order CAUTION To reduce the risk of fire th...

Page 4: ...rage temperature less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety If there are any questions don t hesitate to contact your local EATON representative ...

Page 5: ...llation 18 3 5 Rack Installation 19 3 6 Connecting the EBM s 20 3 7 Detecting other Accessories 21 3 8 UPS Connection without Hotswap MBP Module 22 3 9 Connection with a Hotswap MBP Module Optional Accessory 23 4 4 C Co om mm mu un niic ca at tiio on n 2 25 5 4 1 Communication Ports 25 4 2 UPS Remote Control Functions 26 5 5 O Op pe er ra at tiio on n 3 31 1 5 1 Start up and Normal Operation 31 5 ...

Page 6: ... Equipped with a HotSwap MBP 39 6 5 Recycling The Used Equipment 39 7 7 T Tr ro ou ub blle es sh ho oo ot tiin ng g 4 41 1 7 1 Typical Alarms and Faults 41 7 2 Silencing the Alarm 42 7 3 Service and Support 42 7 4 CE Compliance Contact 43 8 8 S Sp pe ec ciif fiic ca at tiio on ns s 4 45 5 8 1 Model Specifications 45 Table of Contents ...

Page 7: ...ine series representative 1 1 2 2 E En nv viir ro on nm me en nt ta all P Pr ro ot te ec ct tiio on n EATON has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste treatment and facilitate recycling separate the various packing components The cardboard we u...

Page 8: ...uality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Eaton 9PX you can safely eliminate the effects of power disturbances and guard the integrity of your equipment Providing outstanding performance and reliability the Eaton 9PX s unique benefits incl...

Page 9: ...sions D x W x H inch mm Weight lb kg 9PX1500RT L 17 7 x 17 3 x 3 4 450 x 440 x 86 5 35 5 16 2 9PX2000RT L 23 8 x 17 3 x 3 4 605 x 440 x 86 5 50 6 23 0 9PX3000RT L 23 8 x 17 3 x 3 4 605 x 440 x 86 5 52 7 24 0 9PX1500GRT L 17 7 x 17 3 x 3 4 450 x 440 x 86 5 34 8 15 8 9PX2200GRT L 23 8 x 17 3 x 3 4 605 x 440 x 86 5 48 6 22 1 9PX3000GRT L 23 8 x 17 3 x 3 4 605 x 440 x 86 5 50 2 22 8 9PXEBM48RT L 17 6 ...

Page 10: ...tact 4 Connector for additional battery module 5 Primary group outlets for connection of critical equipment 6 Group 1 programmable outlets for connection of equipment 7 Group 2 programmable outlets for connection of equipment 8 Connector for automatic recognition of an additional battery module 9 RS232 communication port 10 USB communication port 11 Connector for ROO Remote On Off control and RPO ...

Page 11: ...A Ac cc ce es ss so or riie es s Table 3 UPS Accessories Part number Description 9PXEBM48RT L 9PXEBM72RT L Extended Battery Module 9RK Rack Kit 9PX Network M2 Network M3 Network Card INDGW M2 Industrial Gateway Card Modbus TCP RTU Relay MS Relay Card 2 2 4 4 C Co on nt tr ro oll P Pa an ne ell The UPS has a five button graphical LCD It provides useful information about the UPS itself load status e...

Page 12: ...A Efficiency 94 Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange Indicator Status Description Green On The UPS is operating normally on Online or on High Efficiency mode Orange On The UPS is on Battery mode Orange On The UPS is on Bypass mode Red On The UPS has an active alarm or fault Control Panel ...

Page 13: ...s Operation status Cause Description Standby mode The UPS is Off waiting for startup command from user Equipment is not powered until button is pressed Online mode The UPS is operating normally The UPS is powering and protecting the equipment Battery mode A utility failure has occured and the UPS is on Battery mode The UPS is powering the equipment with the battery power Prepare your equipment for...

Page 14: ...r Menu function Measurements Load W VA A pf Input Output V Hz Efficiency Battery min V n EBM Battery remaining life months Average power usage Wh Cumulated power Wh BMS Information Control Go to Bypass Transfers the UPS on Bypass mode Load segments On Off Commands the load segments Start battery test Starts a manual battery test Connectivity test Tests dry contact relay outputs and relay card cont...

Page 15: ...tsch Español Русский Português Italiano Simplified Chinese Japanese Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time Date time Format International US US LCD Modify LCD screen brightness and contrast to be adapted to room light conditions Audible alarm Mode Enabled Disabled on battery...

Page 16: ...ynch 5 Unsynch Half cycle Load segments Auto start delay UPS 0s Group1 3s Group2 6s UPS Disabled Auto shutdown delay Group1 Disabled Group2 Disabled Overload prealarm 10 102 Load when overload alarm occurs 102 On Off Settings Start Restart Cold start Auto restart Auto start Start on bypass Cold start Auto restart are Enabled Auto start Start on bypass are Disabled Forced reboot Enabled Disabled En...

Page 17: ...se vs neutral wires swapping Power Off alert Enabled Disabled Enabled If Enabled activates a confirmation screen that requires user confirmation after pressing the power button before the UPS shutdown occurs Battery settings Low battery warning Capacity 0 100 0 Runtime 0min 60min 3min The alarm triggers when the set percentage of battery capacity or remaining back up time is reached Restart bat le...

Page 18: ...will actuate Output signal parameters through external contact connector or RS232 Relay On bat Low bat Bat fault Bypass UPS OK Load protected Load powered General alarm Ext charger ON OVL pre alarm Relay Bypass DB9 1 On bat Low bat Bat fault Bypass UPS OK Load protected Load powered General alarm Ext charger ON OVL pre alarm DB9 1 Low bat DB9 7 On bat Low bat Bat fault Bypass UPS OK Load protected...

Page 19: ... Output OFF No UPS Group 1 Output OFF No Group 2 Group 1 Group 2 OFF delay 0s 999s OFF delay 0s Restart Yes No Restart Yes On battery notice delay Sets delay before noticing on battery information to software 0s General alarm On battery Battery fault Internal fault Overload pre alarm Internal fault Ambient temp Fan lock Bypass overload Current limit Short circuit Inverter overload Power overload L...

Page 20: ...14 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 User Settings ...

Page 21: ...TANT Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your service representative 3 3 2 2 C Ch he ec ck kiin ng g t th he e A Ac cc ce es ss so or ry y K Kiit t Figure 4 9PX1500RT L 9PX2000RT L 9PX3000RT L 14 24 25 21 22 23 17 18 14 9PX UPS 17 RS232 communication cable 18 USB communication cable 21...

Page 22: ...position Elements supplied depending on the version or optional 26 NMC communication card optional standard on Network Bundle options 27 HotSwap MBP module optional 28 Connection cables between Hotswap MBP module and UPS Verify that the following additional items are included with the UPS Figure 6 9PXEBM48RT L 9PXEBM72RT L If you ordered an optional Extended Battery Module EBM verify that the foll...

Page 23: ... the UPS to the utility until installation is complete Figure 7 Internal Battery Connection 1 2 3 5 4 To connect to the UPS 1 Remove the center cover of the front panel 2 Push left cover toward to right direction 3 Open the left side of the front panel NOTE A ribbon cable connects the LCD control panel to the UPS Do not pull on the cable or disconnect it A small amount of arcing may occur when con...

Page 24: ...allation with the UPS To install the cabinet 1 Place the UPS on a flat stable surface in its final location 2 Always keep 6 or 150 mm of free space behind the UPS rear panel for ventilation 3 If installing additional cabinets place them next to the UPS in their final location Adjustment of the orientation of the LCD panel and of the logo Adjustment of the angle of vision of the LCD panel Tower Ins...

Page 25: ...v 02 19 3 3 5 5 R Ra ac ck k I In ns st ta alllla at tiio on n Rack mounting of UPS EBM and accessory modules Follow steps 1 to 4 for module mounting on the rails 1 1 3 3 4 4 2 The rails and necessary hardware are supplied by EATON Rack Installation ...

Page 26: ... 2 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable 3 Connect the battery detection cable s to the connector of the UPS and of the EBM s Figure 8 9PXEBM Rack Mount Connections 9PXEBM48 9PXEBM72 Battery Comm Battery Comm Battery Comm Battery Comm EBM Communications wiring UPS EBM 1 EBM 2 EBM 3 EBM 4 NOTE The EBM communication wiring conn...

Page 27: ... EBM communication wiring connections are directional and must be connected in the correct sequence to ensure proper detection regulation and lifecycle monitoring of the integrated battery management system BMS 3 3 7 7 D De et te ec ct tiin ng g o ot th he er r A Ac cc ce es ss so or riie es s Tip If you ordered other UPS accessories refer to specific user manuals to check the connection to the UP...

Page 28: ...e UPS using the cables 16 It is preferable to connect the priority loads to the outlets marked 5 and the non priority loads to the outlets marked 6 7 that can be programmed Connect any high power devices to the 16 A outlet To program shutdown of outlets 6 7 during operation on battery power and thus optimise the available backup time please check the in out settings 3 For G models fit the cable lo...

Page 29: ...o the AC power source 2 Connect the UPS input cable 1 to the UPS Input socket 35 on the HotSwap MBP module 3 Connect the UPS outlet 5 to the UPS Output 34 on the HotSwap MBP module using the cable 28 supplied for G models These cables and the connectors are marked in red 4 Connect the equipment to the outlets 29 on the HotSwap MBP module These outlets differ depending on the version of the HotSwap...

Page 30: ...lets to directly power equipment As operating the bypass switch 33 will cut supply voltage to the equipment HotSwap MBP module operation 32 33 31 UPS start up with the HotSwap MBP module 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Set switch 33 to Normal position 3 Start the UPS by pressing the ON OFF button on the UPS control panel The load is supplied by the UPS LED 3...

Page 31: ...ftware Installation of the communication cards 2 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 2 secured by screws 2 Insert the communication card in the slot 3 Secure the card cover with the 2 screws Characteristics of the contact RS232 communication port 1 6 7 8 9 300 Ohm R 2 3 4 5 Pin Signal Direction Function 1 Bat Low Output Low Battery...

Page 32: ...parameter see Settings Com Settings Shutdown commands on page 16 the unit may startup automatically IMPORTANT Warning Signal inputs have no function by default please choose a function through the LCD Settings Com settings Input signals See below 2 examples of configuration with RPO terminal used as RPO function and ROO terminal use as ROO function Remote Power Off RPO RPO is used to shutdown the ...

Page 33: ...s Connector type Terminal 14 AWG maximum wires External breaker specification 60 V DC 30V AC 20mA max RPO 11 ROO Remote Control Connection and Test 1 Check the UPS is shut down and the electrical supply network disconnected 2 Remove RPO connector from the UPS by unfitting the screws 3 Connect a normally closed volt free contact between the two pins of connector RPO 11 Normally Closed Contact open ...

Page 34: ...rter with no alarm and ready to go to battery General alarm Choose events that will trigger this alarm trough the LCD Settings Com settings General alarm for more information on possible events please look at page 16 Ext charger ON Control an optional external battery charger on and off OVL pre alarm Overload pre alarm 1 Relay output Normally Closed Normally Open Common 1 2 3 Connectivity Cards Co...

Page 35: ...igent Power Software suite Eaton Intelligent Power Software suite is available from eaton com download Eaton Software suite provides up to date graphics of UPS power and system data and power flow It also gives you a complete record of critical power events and it notifies you of important UPS or power information If there is a power outage and the 9PX UPS battery power becomes low Eaton Software ...

Page 36: ...30 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 UPS Remote Control Functions ...

Page 37: ...e the UPS must have been powered by utility power with output enabled at least once Battery start can be disabled See the Cold start setting in ON OFF Settings in To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The UPS transfers from Standby mode to Battery mode The indicator illuminates solid Th...

Page 38: ...t of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available and your equipment is not protected however the utility power continues to be passively filtered by the UPS The indicator illuminates Depending on overload conditions the UPS remains in Bypass mode for at least 5 seconds and will stay in this mode if three transfers to Bypass occ...

Page 39: ... Bypass only when Bypass is within the following specifications Bypass voltage is between the Bypass Voltage Low Limit and Bypass Voltage High Limit settings Bypass frequency is within nominal frequency 5 You can prohibit Bypass Never or always allow Bypass with no specification checking Always For Always on UPS Fault transfer to Bypass is always made on UPS fault otherwise operation proceeds as w...

Page 40: ...e display 1 Press any button to activate the menu options then select Event log 2 Scroll through the listed events 5 5 1 10 0 R Re et tr riie ev viin ng g t th he e F Fa au ullt t L Lo og g To retrieve the Fault log through the display 1 Press any button to activate the menu options then select Fault log 2 Scroll through the listed faults Retrieving the Event Log ...

Page 41: ... electrical shock or burn from high short circuit current Observe the following precautions 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Wear rubber gloves and boots When replacing batteries replace with the same type and number of batteries or battery packs Contact your service representative to order new ...

Page 42: ... pack See Recycling the used equipment on page 38 for proper disposal 7 Verify that the replacement batteries have the same rating as the batteries being replaced 8 Put the new battery pack into the UPS Push the battery pack firmly reconnect the red and black battery connectors then reconnect the BMS communication cable 9 Verify that all of the alarms have cleared on the display 10 Screw back the ...

Page 43: ...eset 7 If the UPS was shut down during the battery replacement process see 5 1 Start up and Normal Operation 6 6 3 3 B Ba at tt te er ry y S Se et tt tiin ng gs s R Re es se et t After replacement of the internal UPS batteries and extended battery modules the BMS auto setup and battery life settings will need to be reset in the Control menu of the display 1 Reset the BMS auto setup function in the...

Page 44: ...ve alarms or notices Resolve any active alarms before continuing See section 7 1 Typical Alarms and Faults If the indicator is on do not proceed until all alarms are clear 2 Verify that the indicator illuminates solid indicating that the UPS is operating normally and any loads are powered and protected The UPS should be in normal mode See 5 1 Start up and Normal Operation If the UPS internal batte...

Page 45: ... otherwise there is a connection error between the HotSwap MBP module and the UPS 3 Set switch 33 to Normal position The red LED on the HotSwap MBP module goes OFF MBP 120 LOAD 15 28 1 8 2 4 3 5 6 9 10 11 7 29 33 34 35 36 Maintenance 6 6 5 5 R Re ec cy yc clliin ng g T Th he e U Us se ed d E Eq qu uiip pm me en nt t Contact your local recycling or hazardous waste center for information on proper d...

Page 46: ...40 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 Recycling The Used Equipment ...

Page 47: ...ons 2 Press the button to select Event log or Fault log 3 Scroll through the listed events or faults The following table describes typical conditions Conditions Possible cause Action Battery mode LED is On 1 beep every 10 seconds A utility failure has occurred and the UPS is in battery mode The UPS is powering the equipment with battery power Prepare your equipment for shutdown Battery mode LED is...

Page 48: ... If the UPS transferred to Bypass mode the UPS will return to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any heat sources Allow the UPS to cool Ensure the airflow around the UPS is not restricted Restart the UPS If the condition continues to persist contact your service representative The UPS does not s...

Page 49: ...elp Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units IMPORTANT For critical applications immediate replacement may be available Call the Help Desk for the dealer or distributor nearest you 7 7 4 4 C CE E C Co om mp plliia an nc ce e C Co on nt ta ac ct...

Page 50: ...44 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 CE Compliance Contact ...

Page 51: ...VA 2000W 9PX3000GRT L 3000VA 2400W Table 8 Extended Battery Module List Model Configuration Battery Voltage For Power Module 9PXEBM48RT L Rack Tower 48Vdc 1500VA 9PXEBM72RT L Rack Tower 72Vdc 2000 2200 3000VA Table 9 Weights and Dimensions Model Dimensions D x W x H inch mm Weight lb kg 9PX1500RT L 17 7 x 17 3 x 3 4 450 x 440 x 86 5 35 5 16 2 9PX2000RT L 23 8 x 17 3 x 3 4 605 x 440 x 86 5 50 6 23 ...

Page 52: ...r to battery Bypass Voltage Range 20 15 of nominal value default Noise Filtering Input EMC filter Table 11 Electrical Input Connections Model Input Connection Input cable 9PX1500RT L 5 15P 8ft 2 4m 9PX2000RT L 5 20P 8ft 2 4m 9PX3000RT L L5 30P 8ft 2 4m 9PX1500GRT L IEC C14 IEC 10A 6ft 1 8m 9PX2200GRT L IEC C20 16 A inlet L6 20P to C19 jumper provided 6ft 1 8m 9PX3000GRT L Table 12 Electrical Outpu...

Page 53: ...etting on page 14 Battery mode 102 130 12s 130 2s Overload warning then transfer to stop output Output Overload Bypass Mode 102 110 Overload warning 110 130 shutdown after 5mins 130 150 shutdown after 15s 150 shutdown after 300ms Percent is based on nominal current in bypass mode Voltage Waveform Sinewave Harmonic Distortion 3 THDV on linear load 5 THDV on non linear load Transfer Time Online Mode...

Page 54: ...ield 10 V IEC 61000 4 8 Conducted magnetic field 30 A m for output cable 10m Agency Markings CE cULus NOM Energy Star BSMI Operating Temperatures 0 to 40 C 32 to 104 F in Online mode with linear derating for altitude Note thermal protection switches load to Bypass in case of overheating Storage Temperatures 0 to 40 C 32 to 104 F with batteries 25 to 55 C 13 to 130 F without batteries Transit Tempe...

Page 55: ...VA 48Vdc 2200VA 72Vdc 3000VA 72Vdc 9PXEBM48RT 48Vdc 9PXEBM72RT 72Vdc Type Lithium Iron Phosphate LFP battery module Lithium Ion float service life 8 years 25 C Monitoring Integrated battery management system BMS for temperature regulation and life cycle monitoring EBM Battery Cable Length 350 mm 13 78 in Model Specifications ...

Page 56: ...P 16400100602 P 164001006 02 ...

Reviews: