Page 43
9PX3K3U_EN
ENGLISH
9. Specifications
Agency markings
CE / cULus / energy star
Operating temperature
0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note:
thermal protection switches load to Bypass in case of overheating.
Storage temperature
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity
0 to 95% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible noise
< 45 dBA at 1 meter typical
Table 9. Battery
Internal batteries
EBM
Rack / Tower
configuration
9PX3K3U: 180Vdc
9PXEBM180RT: 180Vdc
Type
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30°C.
Monitoring
Advanced monitoring for earlier failure detection and warning
Battery port
External three-pole SBS75G Black connector on UPS for connection to EBM
EBM battery
cable length
40cm (15.7in)
Table 10. Communication options
Communication bay
(1) available independent communication bay for connectivity cards
Compatible connectivity
cards
Network-MS
Modbus-MS
Relay-MS
Communication ports
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Relay output contacts
(4) relay outputs (normally open or normally closed)
Remote On/Off
2 pins jumper (normally open)
Remote Power Off
3 pins jumper (normally open or normally closed)
Summary of Contents for 9PX3K3U
Page 46: ...Page 46 9PX3K3U_EN ...