Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01
29
C
Chhaapptteerr 77 U
UP
PS
S M
Maaiinntteennaannccee
77..11
EEqquuiippm
meenntt C
Caarree
For the best preventive maintenance, keep the area around the equipment clean and dust free. If the
atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the
equipment at an ambient temperature of 25°C (77°F).
If the UPS requires any type of transportation, verify that the UPS is disconnected and turned off. The batteries
are rated for a 8 year service life. The length of service life varies, depending on the frequency of usage and
ambient temperature. Batteries used beyond expected service life will often have severely reduced runtimes.
77..22
S
Sttoorriinngg tthhee EEqquuiippm
meenntt
If you store the equipment for a long period, recharge the battery every 6 months by connecting the UPS to
utility power. The internal batteries charge to 90% capacity in less than 4.7 hours. However, Eaton
recommends that the batteries charge for 48 hours after long-term storage. Check the battery recharge date on
the shipping carton label. If the date has passed and the batteries were never recharged, do not use them.
Contact your service representative.
77..33
R
Reeppllaacciinngg tthhee B
Baatttteerriieess
•
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
•
The internal battery is heavy. Use caution when handling the heavy batteries.
Eaton Lithium-ion UPS batteries have an expected life span of 8 years. After 8 years of operation, the UPS will
provide a battery replacement notification reminding you that your batteries are nearing the end of their useful
life. You should take proactive steps to ensure you replace your batteries for optimal operation and reliability.
Contact your service representative to order new batteries.
-% 100%
-kW 100min
-kVA 1 EBM
Load not powered
8 years battery
Replacement is
recommended
Battery replacement
!
OK
Batteries can be replaced easily without turning off the UPS or disconnecting the load. If you prefer to remove
input power to change the batteries, see
.
Consider all warnings, cautions, and notes before replacing batteries.
•
Servicing should be performed by qualified service personnel knowledgeable of batteries and required
precautions. Keep unauthorized personnel away from batteries.
•
Batteries can present a risk of electrical shock or burn from high short circuit current. Observe the
following precautions:
1.
Remove watches, rings, or other metal objects,
2.
Use tools with insulated handles,
Summary of Contents for 9PX6KIRTN-L
Page 16: ...10 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 User Settings ...
Page 40: ...34 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Recycling The Used Equipment ...
Page 44: ...38 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Compliance Contact ...
Page 49: ...Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 43 Model Specifications EMEA ...
Page 50: ...DPD 9PX220501 DPD 9PX2205 01 ...