102
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
Table 8. Power Ratings (Continued)
Combined UPS
Ratings
Split Phase
Voltage L-N/L-L
Max Input
Current/Phase
Output Current L-
N*
Input Service
Heat Dissipation
— Normal Mode
16KVA, 14400
Watts (4 UPMs)
120/208V or 240V
80
66.68A/phase
100A
3400 BTU/hr
20KVA, 18000
Watts (5 UPMs)
120/208V or 240V
100
83.35A/phase
125A
4250 BTU/hr
*Note: Relative to output load factor, for 120V L to N current
1100..33
C
Ciirrccuuiitt B
Brreeaakkeerrss
Circuit Breakers
Table 9. Circuit Breaker Sizes
Required Input Circuit Breaker Sizes
UPS Capacity
Input Circuit Breaker
4kVA
25A
8kVA
50A
12kVA
75A
16kVA
100A
20kVA
125A
1100..44
EEnnvviirroonnm
meennttaall aanndd S
Saaffeettyy
Table 10. Environmental and Safety
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature
UPS with battery modules: –20°C to +40°C (–4°F to 104°F)
UPS without batteries: –40°C to +60°C (–40°F to 140°F)
Relative Humidity
5–95% noncondensing
Operating Altitude
Up to 3,050 meters above sea level (10,000 ft)
The maximum operating ambient temperature decreases 1°C
per 300m above 1525m (2°F per 1000 ft above 5000 ft)
Non-Operating Altitude
Up to 12,200m above sea level (40,000 ft)
Ventilation
The air around the UPS must be clean and free of dust,
corrosive chemicals, and other contaminants. The Eaton 9PXM
UPS uses internal fans to circulate the air for cooling. The air
must be free to circulate around the UPS and battery cabinet(s).
Do not operate the UPS in a sealed room or container.
Audible Noise
Less than 67 dBA
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...