4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
9
C
Chhaapptteerr 22 IInnssttaallllaattiioonn S
Seettuupp
22..11
P
Prreeppaarriinngg ffoorr IInnssttaallllaattiioonn
This chapter explains how to set up and install the Eaton 9PXM eight and twelve-slot cabinets:
•
Equipment Clearances
•
Location Requirements
•
UPS Setup
•
Anchor Bracket Installation
•
Rack-mount installation
22..22
EEqquuiippm
meenntt C
Clleeaarraanncceess
All cabinet sizes require the following clearances to allow for servicing and adequate ventilation:
•
Sides: 15.2 cm (6")
•
Top: 30.5 cm (12")
•
Front: 91.5 cm (36")
Service Clearance
If flexible conduit connects the UPS to the service input and load distribution panels, you may be able to gain
access for servicing by moving the UPS. If this is the case, you must still leave 30.5 cm (12") clearance at the
back,15.2 cm (6") at the sides 91.5 cm (36") at the front of the UPS for ventilation.
NOTE
Do not block the ventilation holes on each side and the back of the cabinet. Do NOT
attempt to move the cabinet with the power modules or battery modules installed.
External battery cabinets may be installed with bases tight against the UPS cabinet base and against each
other.
22..33
LLooccaattiioonn R
Reeqquuiirreem
meennttss
Install the Eaton 9PXM UPS as close as possible to the equipment or the load distribution panel it will protect.
If a separate external battery cabinet (EBM) is installed, the battery cabinets must be adjacent to the Eaton
9PXM UPS. If the batteries will be farther from the cabinet than the standard cables allow, contact your service
representative or your local distributor for assistance.
UPS cabinet dimensions are located in
.
22..44
U
UP
PS
S S
Seettuupp
The Eaton 9PXM UPS eight and twelve-slot cabinets are shipped on a shipping pallet. Power modules and
battery modules are shipped in separate boxes on another pallet.
NOTE
Installation for the eight-slot cabinets are identical to the twelve-slot cabinets. Twelve-
slot cabinets are shown in these set up instructions.
CAUTION
Do NOT attempt to move the cabinet with the power modules or battery modules installed.
To set up 8– or 12– slot cabinets:
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...