48
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
NOTE
DC input cables only required if EBM(s) are installed upstream.
5.
Close the DC emergency disconnect switch button on the back of each EBM. Insert the switch key
supplied with the cabinet into the button and turn clockwise 1/2-turn. Pull the button OUT to close the
switch and reconnect DC power. Turn the key back counter-clockwise, and remove the key (see
).
Figure 41. EBM Emergency Disconnect Switch
EBM
Disconnect
Switch
!
IMPORTANT
Continue to "
” to set the number of external battery strings on the UPS LCD for
calculating the runtime.
55..22
C
Coonnnneecctteedd B
Baatttteerryy C
Caabbiinneett O
Oppttiioonn
If you are not installing optional battery modules (EBM), continue to “
”.
The Advanced Battery Cabinet for the 9PX allows for the following enhanced installation options:
•
No AC Input Option:
For use for Extended Run-Time Battery Support only.
•
120VAC Single Phase Input Option :
UPS Communication Capable and Extended Run-Time Battery
Support.
•
120V/208V or 120V/240V Split-Phase Input:
Super Charger Capable, UPS Communication Capable and
Extended Run Time Battery Support.
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the battery cabinet installation.
Risk of electrical shock.
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...