4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
53
120VAC Single Phase Input
UPS Communication Capable and Extended Run-Time Battery Support (see
).
NOTE
A 5–15 line cord is included in the EBM accessory kit. Only to be used with this wiring
option.
Figure 46. Single Phase Input
G L1 N
Option #3
120V/208V
or
120V/240V
Split-Phase Input = Super Charger Capable, UPS Communication Capable and
Extended Run-Time Battery Support (see
).
NOTE
For the
120V/208V
or
120V/240V
wiring option the EBM AC input must be installed on
its own dedicated 30 amp circuit. Do not connect the EBM AC input to the UPS.