74
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
77..77..11
A
Addvvaanncceedd B
Baatttteerryy M
Maannaaggeem
meenntt
Advanced Battery Management (ABM) extends the life of the battery by shutting off the charger for 28 days
per ABM cycle and therefore reduces grid corrosion in the battery caused by trickle charging over long periods
of time. Disabling ABM means the battery chargers run in constant charge mode and never turn off. The
battery test period is every three ABM cycles.
NOTE
It is not recommended to perform a battery discharge test more often than 90 days.
77..77..22
A
Auuttoo B
Baatttteerryy TTeesstt
The battery test will run only in Rest Mode and if ABM is enabled. The tests frequency can be modified. During
the test, the UPS transfers to Battery mode and discharges the batteries for 25% battery time remaining.
NOTE
Battery mode is not displayed and battery low alarm does not activate during a battery
test.
The battery test may be postponed due to bad conditions, or failed if battery is not ok.
77..77..33
LLoow
w B
Baatttteerryy W
Waarrnniinngg
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than
the setting capacity threshold (0% by default). This threshold can be modified.
77..77..44
EExxtteerrnnaall B
Baatttteerryy S
Seettttiinngg
The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM
or in Ah.
77..77..55
D
Deeeepp D
Diisscchhaarrggee P
Prrootteeccttiioonn
This setting is recommended to avoid damaging the battery. Warranty is void if deep discharge protection is
disabled
77..88
R
Reettrriieevviinngg tthhee EEvveenntt LLoogg
To retrieve the Event log through the display:
1.
Press any button to activate the menu options, then select Event log (see
).
2.
Scroll through the listed events.
3.
Reset event log if desired.
77..99
R
Reettrriieevviinngg tthhee FFaauulltt LLoogg
To retrieve the Fault log through the display:
1.
Press any button to activate the menu options, then select Fault log (see
).
2.
Scroll through the listed faults.
3.
Reset fault log if desired.
77..1100
C
Coonnttrrooll P
Paanneell O
Oppeerraattiioonn
The control panel provides UPS function and control settings.
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...