Table 5. UPS Recommended Breaker Sizes
UPS Capacity
Input Circuit breaker Rating
75°C Copper Wire Size
4kVA
25A
5.3 mm2 (10 AWG)
8kVA
50A
8.4 mm2 (8 AWG)
12kVA
80A
21.2 mm2 (4 AWG)
16kVA
100A
33.6 mm2 (2 AWG)
20kVA
125A
42.1 mm2 (1 AWG)
NOTE
If a super charger is installed in an EBM, the circuit breaker for the AC input to EBM
must be a 25 A breaker with 5.3 mm2 (10 AWG) copper wire.
NOTE
To accommodate the feature of easy system expendability, it is recommended that
initial installation of the Eaton 9PXM UPS contains wiring to support the maximum
capacity of the UPS cabinet : 20kVA for 12–slot cabinets and 16kVA for 8 slot chassis.
See for recommended conductor sizes to wire the input circuit breakers.
Table 6. UPS Recommended Wire Sizes
Input Breaker Size
75° Copper Wire Size
Conductor Screw Tourqe
25A
5.3 mm2 (10 AWG)
4.0 Nm (35 lb in)
50A
8.4 mm2 (8 AWG)
4.5 Nm (40 lb in)
80A
21.2 mm2 (4 AWG)
5.1 Nm (45 lb in)
100A
33.6 mm2 (2 AWG)
6.6 Nm (50 lb in)
125A
42.1 mm2 (1 AWG)
6.6 Nm (50 lb in)
!
IMPORTANT
FOR U.S. INSTALLATIONS, READ THIS IMPORTANT NOTE
•
lists the mm2 and AWG wire size for each circuit breaker size shown on the wiring diagrams. The
minimum recommended circuit breaker sizes for each model and voltage application are listed on the
wiring diagrams.
•
Conductor sizes shall be no smaller than the 75°C wire size based on the ampacities given in Table 310.15
(B)(16) of the National Electrical Code® (NEC®), ANSI/NFPA 70-2017, and article 220. All circuit
conductors, including the neutral conductor, must be the same size (ampacity) wire. Code may require a
larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or
long service runs. Follow local code requirements.
Summary of Contents for 9PXM
Page 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Page 4: ......
Page 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Page 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Page 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Page 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Page 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Page 130: ...P 16400066909 P 164000669 09 ...