18
1 phase bypass input
D type
230A
≥230A
3 phase bypass input
D type
80A
≥80A
1 phase output
D type
230A
≥230A
3 phase output
D type
80A
≥80A
Cable and connector
The cable’s conductor size should be selected based on the size of the UPS power module.
Refer to the following two tables for the cross-sectional dimensions in mm². Each for 15kvA
and 20kVA UPS respectively:
15kVA UPS
MBP Model
Input/
Output
Mode
Input
Output
Main input
Bypass input
G
ro
u
n
d
w
ir
e
L w
ir
e
N
w
ir
e
L w
ir
e
N
w
ir
e
L w
ir
e
N
w
ir
e
G
ro
u
n
d
w
ir
e
MBP20K
MBP20KPDU
3-1
6
6
16
16
16
16
16
16
3-3
6
6
6
6
6
6
6
6
1-1
35
35
16
16
35
16
16
16
1-3
35
35
6
6
35
6
6
6
MBP20KPARA
3-1
16
16
50
50
50
50
50
50
3-3
16
16
10
10
16
10
10
10
1-1
95
95
50
50
95
50
50
50
1-3
95
95
10
10
95
10
10
10