24
III. Bridge the
‘AC segment terminal L1/L2/L3’ with ‘busbar #3’, then connect the
AC cable(L) to it
3.
Connection to the UPS:
I.
Remove all busbars from the UPS
II.
Connect the UPS to MBP with the
‘Cable to UPS1’ included in the MBP’s
accessory
3.1.3
Mode 3-3(single source)
:
1.
Input:
I. Connect the main-ground cable (PE) to the chassis
II. Bridge the
‘AC input terminal N/N’ with ‘busbar #1’, then connect the AC cable
(N) to it
III.
Bridge the ‘AC input terminal mL1/bL1’ with ‘busbar #1’, then connect the AC
cable (L1) to it