25
IV.
Bridge the ‘AC input terminal mL2/bL2’ with ‘busbar #1’, then connect the AC
cable (L2) to it
V.
Bridge the ‘AC input terminal mL3/bL3’ with ‘busbar #1’, then connect the AC
cable (L3) to it
2.
Output:
I. Connect the ground cable (PE) to the chassis
II. Bridge the
‘AC segment terminal N/N’ with ‘busbar #1’, then connect the AC
cable (N) to it
III. Connect
the ‘AC segment terminals L1/L2/L3’ to the AC cables (L1/L2/L3)
3.
Connection to the UPS:
I. Remove all the busbars of the UPS
II.
Connect the UPS to MBP with the ‘Cable to UPS1’ included in the MBP’s
accessories
3.1.4
Mode 3-3(Dual source)
Summary of Contents for 9SX 15K Series
Page 1: ...1 Eaton 9SX 15 20K Series Maintenance ByPass MBP MBP20K MBP20KPDU MBP20KPARA...
Page 2: ...Copyright 2020 EATON All rights reserved...
Page 50: ...50...
Page 53: ...53 Appendix 1 System block diagram...
Page 55: ......
Page 56: ...614 40048 00...