26
1.
Input:
I. Connect the main-ground cable (PE) to the chassis
II. Bridge the
‘AC input terminal N/N’ with ‘busbar #1’
III. Connect the AC main source cable (N) and bypass source cable with lugs on
top of each other to the aforementioned (N) terminal busbar #1
IV.
Connect the ‘AC input terminals mL1/mL2/mL3’ to the main source cables
(L1/L2/L3)
V. Connect
the ‘AC input terminals bL1/bL2/bL3’ to bypass source cables
(L1/L2/L3)
2.
Output:
I. Connect the ground cable (PE) to the chassis
II. Bridge the
‘AC segment terminal N/N’ with ‘busbar #1’, then connect the AC
cable (N) to it
III.
Connect the ‘AC segment terminals L1/L2/L3’ to the AC cables (L1/L2/L3)
3.
Connection to the UPS:
III. Remove all the busbars of the UPS
IV.
Connect the UPS to MBP with the ‘Cable to UPS1’ included in the MBP’s
accessories