Input:
I. Connect the main-ground cable (PE) to the chassis
II. Bridge the
‘AC input terminal N/N/N’ with ‘busbar #9’, then connect the AC cable
(N), and bypass source cable (N) to it
III.
Connect the ‘AC input terminal mL1/mL2/mL3’ to the main source cable
(L1/L2/L3)
IV.
Connect the ‘AC input terminal bL1/bL2/bL3’ to the bypass source cable
(L1/L2/L3)
2.
Output:
I. Connect the ground cable (PE) to the chassis
II. Bridge the
‘AC segment terminal N/N/N’ with ‘busbar #3’, then connect the AC
cable (N) to it
III.
Connect the ‘AC segment terminal L1/L2/L3’ to AC cable (L1/L2/L3)
3.
Connecting to UPS 1 and UPS 2:
I. Remove all busbars of the UPS
II.
Connect UPS 1 and UPS 2 to the MBP with ‘Cable to UPS 1’ and Cable to UPS
2’ included in the MBP’s accessory