112
5.
After the UPS is powered off again, insert the EPO terminal and power it
on again
•
Press the button for more than 1 second, the buzzer will beep and the
UPS will start up. After a few seconds, the UPS enters the mains
mode.
•
If the utility power is abnormal, the UPS will transfer to Battery mod.
•
When the battery is not connected, the UPS can still be startup. After
the startup, there is alarm of battery not connected. If the utility
power is abnormal, the UPS load will not be protected.
•
The load is powered by the UPS and the LCD shows a charging sign
indicating that the battery is charging.
•
Startup the output device.
Startup the UPS on Battery(Without utility power)
When the UPS is connected to the battery, wait at least 10 seconds
before pressing the power button.
The battery can be turned on or disabled. For details, see 7.3.4 Settings
→
Battery Setting.
Make sure all connections are correct.
•
Press the button for more than 0.1 seconds. The UPS establishes the
power, the fan starts to rotate, the LCD displays the startup animation,
and then enters the main page to display the standby mode.
•
If there is no operation, the LCD is off out after 10 seconds and the UPS is
powered down.
•
Press the button for more than 1 second, the buzzer will beep and the
UPS will startup. The UPS enters battery mode after a few seconds.
•
If the utility power is connected at this time, the UPS will switch to the line
mode and the output will be uninterrupted.
Summary of Contents for 9SX 15KPMAU Series
Page 1: ...Eaton 9SX 15 20KPM CH 系列 在线式 UPS ...
Page 2: ......
Page 10: ...4 2 2 电池箱 电池箱 电池箱 电池箱 EBM 前视图 后视图 功能说明 1 保险丝盒 2 电池连接口 1 3 电池连接口 2 4 RJ45 接口 电池侦测模块 5 外部接地螺丝 ...
Page 60: ...54 附录一 附录一 附录一 附录一 系统框图 系统框图 系统框图 系统框图 ...
Page 62: ...56 附录 附录 附录 附录三 三 三 三 有害物质表 有害物质表 有害物质表 有害物质表 ...
Page 63: ...Eaton 9SX 15 20KPM AU Series Online UPS Eaton DXRT15 20KS IN Series Online UPS ...
Page 64: ...Copyright 2019 EATON All rights reserved ...
Page 127: ......
Page 128: ...121 614 40045 00 ...