Page 14
5-6kVA EU_EN
2. Presentation
Submenu
Available settings
Default settings
In/Out settings
Interrupt time
If Bypass transfer is enabled,
Interrupt time: [10ms] [20ms]
Define break duration when transfer
on Bypass
[10ms]
Overload
prealarm
[10%] … [102%]
Load % when overload alarm occurs
[102%]
Redundancy
mode
[Unitary UPS] [Hot Standby]
Force slew rate value to 0.5Hz/s
Unitary UPS
On/Off settings
Cold start
[Enabled] [Disabled]
Authorize the product to start on
battery power.
[Enabled]
Forced reboot
[Enabled] [Disabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown
sequence will not complete and
restart will occur immediately.
[Enabled]
Auto restart
[Enabled] [Disabled]
Authorize the product to restart
automatically when mains recovers
after a complete battery discharge.
[Enabled]
Auto start
[Enabled] [Disabled]
The UPS automatically starts up as
soon as mains power is available
(no need topress the
button).
[Disabled]
Energy saving
[Disabled] [100W] … [1000W]
If Enabled, UPS will shutdown after
5 min. of back-up time, if load is less
than threshold.
[Disabled]
Sleep mode
[Enabled] [Disabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS
is OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled]
Remote command
[Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled]
Bypass standby
[Enabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
[Enabled]
Battery settings
Automatic battery
test
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
[Every ABM cycle]
Low battery
warning
[0%] ... [100%]
The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
[20%]
Restart bat. level
[0%] ... [100%]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
[0%]
Battery charge
mode
[ABM cycling] [Constant charge]
[ABM cycling]
External battery
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
[No battery]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
Deep Disch.
protect.
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Warranty void if set to No.
[Yes]