SAFETY INSTRUCTIONS

Safety of persons

•  The system has its own power source (the battery). Consequently, the power outlets may be ener-

gized even if the systems is disconnected from the AC power source. Dangerous voltage levels are 

present within the system. It should be opened exclusively by qualified service personnel.

•  The system must be properly grounded. 
•  The battery supplied with the system contains small amounts of toxic materials.  

To avoid accidents, the directives listed below must be observed:
-  Servicing of batteries should be performed or supervised by personnel knowledgeable about bat-

teries and the required precautions.

- When replacing batteries, replace with the same type and number of batteries or battery packs.

- Do not dispose of batteries in a fire. The batteries may explode.

- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.

•  Precautions must be taken for all handling: 

- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries. 
- Disconnect charging source prior to connecting or disconnecting battery terminals.
-  Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from 

ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood 

of such shock can be reduced if such grounds are removed during installation and maintenance 

(applicable to equipment and remote battery supplies not having a grounded supply circuit).

Product safety

•  The UPS connection instructions and operation described in the manual must be followed in  

the indicated order.

• 

CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with branch circuit 

 

overcurrent protection for : 30A rating, for 5-6kVA models in accordance with the National Electric 

Code, ANSI/NFPA 70 (US installations only). 

The upstream circuit breaker must be easily accessible.  

The unit can be disconnected from AC power source by opening this circuit breaker.

•  Disconnection and overcurrent protection devices shall be provided by others for permanently 

connected AC input/output circuits.

•  Check that the indications on the rating plate correspond to your AC powered system and  

to the actual electrical consumption of all the equipment to be connected to the system.

•  For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall  

be easily accessible

•  Never install the system near liquids or in an excessively damp environment.
•  Never let a foreign body penetrate inside the system.
•  Never block the ventilation grates of the system.
•  Never expose the system to direct sunlight or source of heat.
•  If the system must be stored prior to installation, storage must be in a dry place.
•  The admissible storage temperature range is -15ºC to +50ºC.
•  The system is not for use in a computer room AS DEFINED IN the standard for the Protection  

of Information Technology Equipment, ANSI/NFPA 75 (US installations only).

 

 Contact Eaton resellers to order a special battery kit, if needed to meet the ANSI/NFPA 75 require-

ment.

Summary of Contents for 9SX 6000VA

Page 1: ...Eaton 9SX 6000VA RT3U 9104 12567...

Page 2: ...H 9SX 5000 9SX 6000 9PX 5000 9PX 6000 9SX EBM 180V 9PX EBM 180V Installation and user manual Copyright 2013 EATON All rights reserved Service and support Call your local service representative 5 6kVA...

Page 3: ...ense Certification standards Safety IEC EN 62040 1 Ed 1 2008 UL 1778 4th edition EMC IEC EN 62040 2 Ed 2 2006 FCC part 15 Class A Performance IEC EN 62040 3 Ed 2 0 2011 IEC 61000 4 2 ESD level 3 IEC 6...

Page 4: ...d remote battery supplies not having a grounded supply circuit Product safety The UPS connection instructions and operation described in the manual must be followed in the indicated order CAUTION To r...

Page 5: ...t low height keep the unit horizontal during unpacking Before and after the installation if the UPS remains de energized for a long period the UPS must be energized for a period of 24 hours at least o...

Page 6: ......

Page 7: ...ess to terminal blocks 23 4 2 Input Output connection 23 5 Operation 24 5 1 UPS startup and shutdown 24 5 2 Operating modes 25 5 3 Transferring the UPS between modes 25 5 4 Setting High Efficiency mod...

Page 8: ...use comprises over 50 of recycled cardboard Sacks and bags are made of polyethylene Packing materials are recyclable and bear the appropriate identification symbol 01 PET Materials Abbreviations Numb...

Page 9: ...tegrity of your equipment Providing outstanding performance and reliability the Eaton 9SX and 9PX s unique benefits include True online double conversion technology with high power density utility fre...

Page 10: ...Dimensions inch mm D x W x H 9SX 5000 106 48 27 0 x 17 3 x 5 1 685 x 440 x 130 9SX 6000 106 48 27 0 x 17 3 x 5 1 685 x 440 x 130 9PX 5000 106 48 27 0 x 17 3 x 5 1 685 x 440 x 130 9PX 6000 106 48 27 0...

Page 11: ...for 9PX only 7 Connector for RPO Remote Power Off control 8 Slot for optional communication card 9 Connector for additional battery module 10 Primary group 16A outlets for connection of critical equip...

Page 12: ......

Page 13: ...nd network card Relay MS INDRELAY MS Relay card MBP6Ki HotSwap MBP 6000i TFMR11Ki Transformer 11000i BINTSYS Battery Integration System EBMCBL180 1 8m cable 180V EBM MBP6Ki 5 3 4 1 2 6 1 Input Output...

Page 14: ...BM 50 2 7kW 3 0kVA Efficiency 95 Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange The following table shows the indicator status and description Indicator...

Page 15: ...UPS is operating normally The UPS is powering and protecting the equipment Battery mode 1 beep every 10 seconds A utility failure has occured and the UPS is on Battery mode The UPS is powering the eq...

Page 16: ...dentification Product type model Part Serial number UPS NMC firmware Com card IPv4 Com card IPv6 Com card MAC Detected accessories Register product Links to Eaton registration website 2 7 User setting...

Page 17: ...after 5 min of back up time if load is less than threshold Disabled Sleep mode Enabled Disabled If Disabled LCD and communication will turn OFF immediately after UPS is OFF If Enabled LCD and communic...

Page 18: ......

Page 19: ...ng the cabinet Unpacking the cabinet in a low temperature environment may cause condensation to occur in and on the cabinet Do not install the cabinet until the inside and outside of the cabinet are a...

Page 20: ...ommunication cable 9 USB communication cable 10 User manual 11 Safety instructions If you ordered an optional Extended Battery Module EBM verify that the following additional items are included with t...

Page 21: ...le s into the battery connector s Up to 6 EBMs may be connected to the UPS 2 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable 3 Connect th...

Page 22: ...he LCD panel If you ordered other UPS accessories refer to specific user manuals to check the tower installation with the UPS To install the cabinet 1 Place the UPS on a flat stable surface in its fin...

Page 23: ...rews to open the left side of the front panel 3 Remove the two screws to pull out the metal protection cover of the battery A ribbon cable connects the LCD control panel to the UPS Do not pull on the...

Page 24: ......

Page 25: ...5 6kVA EU_EN Rack mounting of UPS EBM and accessory modules Follow steps 1 to 4 for module mounting on the rails 1 1 3 4 4 3 2 The rails and necessary hardware are supplied by EATON optional 3 Instal...

Page 26: ...D curve 32A 2 poles circuit breaker G N L2 L1 N L2 L1 to UPS Normal AC source Do not use 30 mA RCD ELCB breaker upstream the UPS 2 Recommended cable cross sections Terminal position Wire function Ter...

Page 27: ...ement SEA Change in SEA between upstream and downstream or galvanic isolation required 12 11 10 13 12 11 10 13 13 13 or Normal AC Load Main low voltage switchboard MLVS Isolation transformer Normal AC...

Page 28: ...on check that the upstream protection device Normal AC source is open O Off Always connect the ground wire first If you ordered a HotSwap MBP refer to the specific user manual to check the terminal bl...

Page 29: ...t the alarms and restart if necessary 7 Verify that the indicator illuminates solid indicating that the UPS is operating normally and powe ring the output The UPS should be in Online mode The internal...

Page 30: ......

Page 31: ...pass mode In the event of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available and your equipment is not protected however the utility pow...

Page 32: ...P AC NOK and Enter to confirm If Enabled the UPS transfers to Bypass even if Bypass AC source is out of tolerance depending on output mode If Disabled the UPS output is shutdown Interrupt time This se...

Page 33: ...ugh the display 1 Press any button to activate the menu options then select Event log 2 Scroll through the listed events 5 8 Retrieving the Fault log To retrieve the Fault log through the display 1 Pr...

Page 34: ...ted Pin 3 not low battery Pin 4 not on Battery Pin 5 user common Pin 6 on Bypass Pin 7 low battery Pin 8 load protected Pin 9 on Battery n o contact normally open n c contact normally closed The relay...

Page 35: ...ge SELV circuit This circuit must be sepa rated from any hazardous voltage circuits by reinforced insulation The RPO must not be connected to any utility connected circuits Reinforced insulation to th...

Page 36: ......

Page 37: ...wn contact to test the function Always test the RPO function before applying your critical load to avoid accidental load loss Connectivity Cards Connectivity cards allow the UPS to communicate in a va...

Page 38: ...slot 3 Secure the card cover with the 2 screws 6 2 Eaton Intelligent Power Software suite Eaton Software suite provides up to date graphics of UPS power and system data and power flow It also gives y...

Page 39: ...Replace batteries at least every 4 years to keep units running at peak efficiency 7 2 Storing the equipment If you store the equipment for a long period recharge the battery every 6 months by connecti...

Page 40: ...n replacing batteries replace with the same type and number of batteries or battery packs Contact your service representative to order new batteries Proper disposal of batteries is required Refer to y...

Page 41: ...panel to the UPS Do not pull on the cable or disconnect it 4 Pull out the plastic handle of the battery pack and slide the pack out slowly on to a flat and stable surface Use two hands to support the...

Page 42: ......

Page 43: ...mly 3 Plug the EBM cable s into the battery connector s Up to 6 EBMs may be connected to the UPS 4 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for e...

Page 44: ...Go to Bypass Bypass LED should be On 5 Turn the HotSwap MBP switch to the Normal position the red LED on the HotSwap MBP goes Off indicating that the load is now powered by the UPS 6 Select Control t...

Page 45: ...ery mode and the battery is running low This warning is approximate and the actual time to shutdown may vary significantly Depending on the UPS load and number of Extended Battery Modules EBMs the Bat...

Page 46: ...ure the airflow around the UPS is not restricted Restart the UPS If the condition continues to persist contact your service representative LED is On 1 beep every 3 seconds The UPS does not start The i...

Page 47: ...service Model number Serial number Firmware version number Date of failure or problem Symptoms of failure or problem Customer return address and contact information If repair is required you will be...

Page 48: ......

Page 49: ...x 17 3 x 5 1 106 48 9PX6Ki 685 x 440 x 130 27 0 x 17 3 x 5 1 106 48 Model EBM Dimensions D x W x H mm in Weight lb kg 9SXEBM180RT 645 x 440 x 130 25 4 x 17 3 x 5 1 150 68 9PXEBM180 645 x 440 x 130 25...

Page 50: ...alarm 125 150 UPS shuts down after 1 minute 150 UPS shuts down after 1s Voltage waveform Sinewave Harmonic distortion 2 THDV on linear load 5 THDV on non linear load Transfer time Online mode 0 ms no...

Page 51: ...000 6000VA 180Vdc 15 x 12V 5Ah 9SXEBM180RT 9PXEBM180 180Vdc 2 x 15 x 12V 5Ah Fuse 63A 63A Type Sealed maintenance free valve regulated lead acid with minimum 3 year float service life at 25 C 77 F Lif...

Page 52: ...battery power Load Devices or equipment connected to the UPS output HE mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user T...

Page 53: ...Page 44 5 6kVA EU_EN...

Page 54: ......