Page 33
614-20306-00 - 9SX 0-6 KVA EMEA_EN
Submenu
Available settings
Default settings
Battery settings
Automatic battery
test
In ABM
®
cycling mode:
[No test] [Every ABM
®
cycle]
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
[Every ABM
®
cycle]
[Every week]
Low battery
warning
[Capacity] [0%] … [100%]
[Runtime] [0min] … [60min]
The alarm triggers when the set
percentage of battery capacity or
remaining back-up time is reached.
[0%]
[3min]
Restart bat. level
[0%] ... [100%]
If set, automatic restart will occur only
when percentage of battery charge is
reached.
[0%]
Battery charge
mode
[ABM
®
cycling] [Constant charge]
[ABM
®
cycling]
External battery
[Auto detection] [Manual EBM set.]
[Manual battery set.]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
Deep Disch.
protect.
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time voltage
threshold.
Warranty void if set to No.
[Yes]
Com settings
Input signals
[RPO] [DB9-4]
Sets Input signals parameters (function,
delay, operation) through external
contact connectors or RS232 port.
RPO port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s]
- [Active]: [Open] [Closed]
DB9-4 port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s]
- [Active]: [High] [Low]:
[No]
[0s]
[Open]
[No]
[0s]
[High]
4. Interfaces and Communication