Specifications
Eaton Advanced ePDU User’s Guide P-164000042—Rev 1
www.eaton.com/ePDU
112
Overcurrent Protection
Table 25 lists the overcurrent protection requirements for the ePDU models with outlet groups protected by
circuit breakers.
Environmental and Safety
Table 26 lists the environmental specifications for all ePDU models.
Table 27 lists safety information for all ePDU models.
Table 24. Output Current Ratings (All ePDU Models)
Outlets
VDE
UL/CSA (Derated)
IEC 60320 C13
10A
12A
IEC 60320 C19
16A
16A
Table 25. Overcurrent Protection
Model
Breaker Qty
Breaker Type
Breaker Rating (A)
Note
eSWA04
2
SP
16
IEC/EN 60934 clearance and creepage distance > 3 mm
eAMA09
2
SP
16
IEC/EN 60934 clearance and creepage distance > 3 mm
eMAA13
2
2P
16
IEC/EN 60934 clearance and creepage distance > 3 mm
eAM001
2
DP
20
UL 489/CSA C22.2 No. 5.1
eAM003
3
DP
20
UL 489/CSA C22.2 No. 5.1
eAM004
3
DP
20
UL 489/CSA C22.2 No. 5.1
eAM005
6
DP
20
UL 489/CSA C22.2 No. 5.1
eMA007
3
DP
20
UL 489/CSA C22.2 No. 5.1
eMA009
6
DP
20
UL 489/CSA C22.2 No. 5.1
eMA010
2
DP
20
UL 489/CSA C22.2 No. 5.1
eMA011
3
DP
20
UL 489/CSA C22.2 No. 5.1
eMA014
3
DP
20
UL 489/CSA C22.2 No. 5.1
Table 26. Environmental Specifications (All Advanced ePDU Models)
Operating Temperature (Room Ambient)
0
°C
to 50
°C
(32
°F
to 122
°
F)
Shipping and Storage Temperature
-25
°C
to 70
°C
(-13
°F
to 158
°
F)
Localized Air Temperature (Inside ePDU)
70
°C
(158
°
F) maximum
Relative Humidity
5–95% noncondensing
Operating Altitude
Up to 3,048m (10,000 ft) above sea level
(derated for higher altitude applications)
Shipping and Storage Altitude
Up to 12,200m (40,000 ft) above sea level
Table 27. Safety Specifications (All Advanced ePDU Models)
Safety Conformance
UL 60950-1, CSA 60950, C22.2 No.29 & No.31 (CSA), IEC/EN60950-1, NEC-NFPA 70
Safety Conformance (Breakers and Outlets)
Outlets: UL 498, IEC 60320-1
Breakers: UL 489
EMC (Class A), North American models
FCC 47 CFR 15, Subpart B: 2009; ICES-003
EMC (Class A), EMEA models
EN 55022: 2007, CISPR 22: 2008, EN 55024: 1998 + A2: 2003, CISPR24: 2002, AS/NZS CISPR 22: 2006