Maintenance and Troubleshooting
Eaton Advanced ePDU User’s Guide P-164000042—Rev 1
www.eaton.com/ePDU
98
Serial Interface
To enable Firmware Upgrade mode from the Serial interface:
1.
Access the interface (see Chapter 8, “Serial Interface Operation” on page 81).
2.
Type
1
(Network Management Card Settings) and press [Enter].
3.
Type
2
(Network Settings) and press [Enter].
4.
If you want to use the IPv4 address, type
1
(IPv4 Configuration) and press [Enter].
5.
If you want to use the IPv6 address, type
2
(IPv6 Configuration) and press [Enter].
6.
Note the IPv4 or IPv6 address.
7.
Type
0
(Return to previous menu) and press [Enter].
8.
Type
3
(Communication Control) and press [Enter].
9.
Type
3
(FTP Upgrade Control) and press [Enter].
10. Type
1
(Enabled) and press [Enter].
11. The FTP Upgrade Control must be enabled as follows (see Figure 73):
Figure 73. Enable FTP Upgrade Control
12. Type
0
(Return to previous menu) and press [Enter].
13. Type
0
(Return to previous menu) and press [Enter].
14. Type
0
(Return to previous menu) and press [Enter].
15. Type
0
(Return to previous menu) and press [Enter].
16. Type
4
(Firmware Upgrade mode) and press [Enter].
17. Type
Y
to confirm the action and press [Enter].
18. The Network Management Card restarts automatically in the Firmware Upgrade mode. Continue to
“Upload New Firmware Files” on page 99.