Specifications
Eaton Advanced ePDU User’s Guide P-164000042—Rev 1
www.eaton.com/ePDU
111
Electrical Ratings
Table 23 and Table 24 list the electrical ratings for the ePDU models.
eMA014
MA
3P
IEC 60309
532P6W
12
12
* Type definitions: AM = Advanced Monitoring (outlet monitoring only); MA = Managed (outlet monitoring and control); SW = Switched (outlet control only)
** Detachable input cords have an input locking mechanism to secure the cord. See “Three-Phase Configurations” on page 37 for an explanation of input connector
codes for three-phase configuration topologies.
Table 22. Electrical Input and Output (By Model) (Continued)
Model
Type *
Phases
Input Cord
Detachable Input Cord
(accessory) **
C13 Outlets
C19 Outlets
Table 23. Electrical Ratings
Model
Input Voltage
Output Voltage
Input Current (A)
Input Current
Derated UL (A)
Maximum Power (kVA)
eSWA01
200–240V
200–240V
10
—
2.4
eSWA02
200–240V
200–240V
16
—
3.8
eSWA03
200–240V
200–240V
16
—
3.8
eSWA04
200–240V
200–240V
32
—
7.7
eSWA05
200–240V (L-N)/
346–415V (L-L)
200–240V
16
—
11.5
eAMA06
200–240V
200–240V
10
—
2.4
eAMA07
200–240V
200–240V
16
—
3.8
eAMA08
200–240V
200–240V
16
—
3.8
eAMA09
200–240V
200–240V
32
—
7.7
eMAA10
200–240V
200–240V
10
—
2.4
eMAA11
200–240V
200–240V
16
—
3.8
eMAA12
200–240V
200–240V
16
—
3.8
eMAA13
200–240V
200–240V
32
—
7.7
eMAA14
200–240V (L-N)/
346–415V (L-L)
200–240V
16
—
11.5
eAM001
200–240V
200–240V
30
24
5.8
eAM002
200–240V
200–240V
20
16
5.8
eAM003
200–240V
200–240V
50
35
12.6
eAM004
200–240V
200–240V
30
24
8.6
eAM005
200–240V
200–240V
60
48
17.3
eAM008
100–240V
100–240V
20
16
3.3
eMA006
200–240V
200–240V
20
16
5.8
eMA007
200–240V
200–240V
50
35
12.6
eMA009
200–240V
200–240V
60
48
17.3
eMA010
200–240V
200–240V
30
24
5.8
eMA011
200–240V
200–240V
30
24
8.6
eMA012
100–240V
100–240V
20
16
3.3
eMA013
200–240V/346–415V
200–240V (L-N)/
346–415V (L-L)
20
16
11.5
eMA014
200–240V/346–415V
200–240V (L-N)/
346–415V (L-L)
30
24