Operation Overview
Eaton Advanced ePDU User’s Guide P-164000042—Rev 1
www.eaton.com/ePDU
53
Environmental Settings Table
Table 12 provides settings for the Environmental Monitoring Probe (EMP).
Table 12. Environment Settings
Name
Description
Temperature Unit
The user can define the temperature unit as follows:
l
°
F
l
°C
(default)
Temperature High Warning Threshold
High warning threshold for the temperature.
The unit of this setting is defined by the temperature unit setting.
In the range [0°C-70°C]
Temperature High Warning Threshold < Temperature High Critical Threshold.
Default is 50
°
C.
If the measurement exceeds this limit:
l
An alarm is set
l
Traps are sent to configured receivers
l
E-mail is sent to configured receivers
l
The high warning icon is displayed near the measurement value in the Web interface
Temperature High Critical Threshold
High critical threshold for the temperature.
The unit of this setting is defined by the temperature unit setting.
In the range [0°C-70°C].
Temperature High Critical Threshold > Temperature High Warning Threshold.
Default is 80°C.
If the measurement exceeds this limit:
l
An alarm is set
l
Traps are sent to configured receivers
l
E-mail is sent to configured receivers
l
The high critical icon is displayed near the measurement value in the Web interface
Humidity High Warning Threshold
High warning threshold for the humidity (measured in percent).
In the range [0%-100%].
Default is 65%.
Humidity High Warning Threshold < Humidity High Critical Threshold.
If the measurement exceeds this limit:
l
An alarm is set
l
Traps are sent to configured receivers
l
E-mail is sent to configured receivers
l
The high warning icon is displayed near the measurement value in the Web interface
Humidity High Critical Threshold
High critical threshold for the humidity (measured in percent).
In the range [0%-100%].
Default is 90%.
Humidity High Critical Threshold > Humidity High Warning Threshold.
If the measurement exceeds this limit:
l
An alarm is set
l
Traps are sent to configured receivers
l
E-mail is sent to configured receivers
l
The high critical icon is displayed near the measurement value in the Web interface