Access Power Solutions Installation and Operation Guide (APS3-330 Series)
96
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-07A1 July 2018
Test
Test procedure
Adjustment
Multiple Rectifier
comms lost
•
Remove 2 rectifiers from the system.
•
Ensure alarm operates.
Partial AC Fail
•
Turn off the ac to more than 20% of the rectifiers in the
system.
•
Ensure alarm operates.
AC Fail
•
Turn off all ac to the system.
•
Ensure alarm operates.
System Overload
•
Reduce the
System Overload Recognition Period
to 0 minutes.
•
Apply load to the system.
•
Turn off rectifiers until the
System Overload Threshold
is
exceeded.
•
Ensure alarm operates.
Load Fuse Fail
Note 2
•
Apply load to the system.
•
Turn off the MCB feeding the load bank.
•
Ensure alarm operates.
Battery Fuse Fail
•
Turn off a Battery MCB or remove a Battery Fuse.
•
Ensure alarm operates.
Battery Test Fail
•
See Battery Test in the System Controller Operation
Handbook for details.
MOV Fail
•
Remove a MOV cartridge from the MOV housing (if fitted).
•
Ensure alarm operates.
ACD Fan Fail
•
Stop the ACD Fan (if fitted).
•
Ensure alarm operates.
LVD alarms
•
See LVD test on page
Battery Temperature
Low
•
Increase the
Battery Temperature Low Threshold
above the
current temperature.
- or -
•
Cool the temperature sensor until the threshold is
exceeded.
•
Ensure alarm operates.
Battery Temperature
High
•
Reduce the
Battery Temperature High Threshold
below the
current temperature.
- or -
•
Heat the battery temperature sensor until the threshold is
exceeded.
•
Ensure alarm operates.
Sensor Fail
•
Disconnect the battery temperature sensor from the I/O
board (XH7).
•
Ensure alarm operates.
•
Replace the battery temperature sensor.
•
Disconnect the current sensor (XH6).
•
Ensure alarm operates.
•
Replace the current sensor.
•
Disconnect the voltage sensor (XH9).
•
Ensure alarm operates.
•
Replace the voltage sensor.