Access Power Solutions Installation and Operation Guide (APS3-330 Series)
62
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-07A1 July 2018
Step 5 - Check the system controller operation
If there is only one IO Board in the system, this IO Board will be automatically
mapped as IOB 1. If more than one IO Board is present, follow the procedure below:
1
Map the I/O board :
•
In DCTools/Web go to:
RXP
.
•
Copy the I/O board serial number(s) from the
RXP Devices
table to the
I/O
Board to Serial Number Mapping
table to map an
IOB Number
to each I/O board
(overwrite an existing serial number if required).
If multiple SiteSure-3G modules are connected use the I/O board Identify function to
physically identify each module. See details in the System Controller Operation
Handbook.
2
Check that the system controller has registered all rectifiers.
3
Check all control processes, alarms and current measurement(s).
4
Check the power system identification parameters and communications settings.
5
Change the configuration file as required to ensure that the system controller
operates as intended.
6
Check the system controller time . See details in the System Controller Operation
Handbook.
Step 6 - Clear LVD Characterization Alarm (if required)
Ignore this step if there is no LVD Characterization alarm.
If the system controller indicates an
LVD Characterization Error
alarm, then:
1
On the SC300 go to: Battery > LVDs > LVD x > Not Characterized > Edit.
2
If available, select
Characterize With IOB Values
. Press
Enter
. No further action is
needed.
3
If
Characterize With IOB Values
if not available, the LVD must be characterized.
This will cause the LVD contactor to disconnect the battery for a few seconds.
The load equipment will be powered by the rectifiers.
•
On the SC300 go to: Battery > LVDs > LVD x > Not Characterized > Edit.
•
Select
Characterize
. Press
Enter
.
The LVD contactor will disconnect and connect. When the characterization is
complete the LVD Characterization Error alarm will clear.
Procedure complete
Return the faulty system controller with a completed Equipment Incident Report on page