Connector
Type
Purpose
Pin
Description
4
Temp Sense 1+
5
Temp Sense 1-
6
-
7
Temp Sense 2+
8
Temp Sense 2-
XH8
MTA
156
LVD Power
1
Bus live
2
Bus common
XH9
MTA
156
Bus Voltage Sense Input
1
Controller reference (Bus live)
2
Controller sense (Bus common)
XH12A
MTA
156
Battery Mid-point
Monitoring sense inputs
Sensor signal is referenced to
live bus.
1
String 1 Mid-point / Quarter-point 1
2
String 2 Mid-point / Quarter-point 2
3
String 3 Mid-point / Quarter-point 3
4
String 4 Mid-point / Quarter-point 4
XH15A
Digital inputs D1-D3
Digital input signals are
referenced to live bus.
1
D1 input
2
0V
3
D2 input
4
0V
5
D3 input
6
0V
XH15B
Digital inputs D4-D6
Digital input signals are
referenced to live bus.
1
D4 input
2
0V
3
D5 input
4
0V
5
D6 input
6
0V
XH15D
Digital inputs D10-D13
IOBGP-10/11 only
Digital input signals are
referenced to live bus.
1
D11 input
2
0V
3
D12 input
4
0V
5
D13 input
6
0V
XH16/XH17
Digital relay outputs 1-2
Digital outputs are
voltage-free.
1
Relay 1 normally closed (NC)
2
Relay 1 normally open (NO)
3
Relay 1 Common (COM)
4
Relay 2 normally closed (NC)
5
Relay 2 normally open (NO)
6
Relay 2 Common (COM)