5.3 The wiring diagram
Remark:
1. The input N wire of the UPS must be connected correctly.
2. One battery pack of the 3A3 Pro UPS consists of 32-40 batteries in series , 40PCS configuration is illus-
trated as an example in Fig. 5-2.
which is divided into two parts by a neutral wire connecting to the middle
of the pack (where the No. 20 and No. 21 batteries are connected). Therefore there are altogether three wires
connected with the UPS terminal blocks including the positive and negative wires of the battery pack. The
battery cables should connect to a DC breaker firstly and then it can be connected to the terminal block of the
UPS. Please refer to the following wire connection diagram for detailed information.
Note: the three wires of the battery pack should be connected to the UPS correctly according to the
marks, otherwise, it may cause hazards of battery short circuit. So make sure to double-check them before
connection. It is required to use DC breakers complying with the safety requirements due to a multiple
quantity of batteries in series.
N
-
Fig. 5-1 The wiring diagram
Fig. 5-2 Sketch map of Battery connected
Summary of Contents for ARRAY 3A3 Pro
Page 1: ...ARRAY 3A3 Pro UPS...
Page 2: ......
Page 3: ...UPS...
Page 5: ...1 2 3 4 5 UPS 6 7 8 9 UPS UPS 1 2 UPS UPS 3 Eaton 1 UPS 2 3 4 A B C D E 5 6 7...
Page 6: ...1 a 0 40 20 90 b c 2 UPS 25 55 UPS 0...
Page 7: ...UPS UPS UPS UPS 01 03 05 08 11 16 18 21 31 33 35 37 39 40 41...
Page 10: ...3 2 1 1 2 1 2 2 2 3 2 3 4 2 4 5 2 5 2 2 2 1 2 3 2 4 2 5...
Page 11: ...4 2 8 2 2 2 6 2 7 UPS 1 2 6 2 UPS 2 7 3 UPS 2 8...
Page 12: ...5 3 1 UPS 120kVA 3 1 LCD UPS UPS 3 2 150kVA...
Page 13: ...6 3 4 120K 3 6 150K 3 3 120K 3 5 150K...
Page 14: ...7 3 2 UPS 3 7 3 10 3 8 3 9...
Page 16: ...9 1 2 3 M8 4 2 4 2 4 1 4 3 4 3 4 UPS 4 3 D1 D2 D3...
Page 17: ...10 5 UPS 6 4 4 7 4 6 UPS UPS 4 5 8 M6 4 5 9 UPS 4 4 4 5 3U 2 2U...
Page 20: ...13 UPS 1 1 UPS N 2 3A3 Pro UPS 32 40 40 3 UPS UPS 5 4 5 2 5 3 N...
Page 21: ...14 2 1 5 6 2 UPS 5 7 3 4 5 6 5 7 UPS 5 4 5 5 UPS...
Page 22: ...15 1 5 8 2 UPS 5 9 3 5 8 5 9 150kVA 1 2 5 10 3 UPS 5 11 4 5 10 UPS 5 11 UPS...
Page 26: ...19 7 2 UPS 1 1 ON 6 2 2 UPS 7 3 6 3 4 5 7 4 1 ENTER 1111 1234 7 3 7 4...
Page 27: ...20 1 UPS UPS 2 EPO 3 4 7 3 10 UPS UPS ENTER 1 2 1111 1234...
Page 28: ...21 8 1 UPS UPS UPS UPS ID ID English 14 UPS LCD LCD LCD 13 10 10 5 11 3V...
Page 30: ...23 UPS 1 2 3 1 2 3 1 2 UPS 3 UPS 4 UPS 10 UPS...
Page 31: ...24 UPS UPS 8 3 a b 45 0 45 0...
Page 32: ...25 7 2 7 3 1111 1234 8 4 35 35 a b 35 35 45 0...
Page 33: ...26 UPS 8 5 ID ID 0 65535...
Page 34: ...27 8 6 YYYY MM DD hh mm ss xxx xxx ID ID 0 65535 CSB UPM1 UPM10 0 65535 14 8 6 1...
Page 35: ...28 10 60min 0 9000s 10s LCD 1 100 13 400 830 3938 800 830 3938 13666666666 13888888888...
Page 36: ...29 8 6 2 45 18 18 Panasonic_100AH 15 15 5 5 10 10 242V 198V...
Page 37: ...30 XCP USB BUS 8 7...
Page 38: ...31 UPS 400 889 3938 UPS 1 1 UPS UPS 2 9 1 1 UPS 2 3 UPS 9 1 UPS 9 2 9 3 9 1...
Page 43: ...36 2 1 LCD 6 LCD 11 3...
Page 46: ...39 24 400 889 3938 www eaton com powerquality upsservice eaton com...
Page 47: ...40 _ _ 1 4 2 1 2 3 4 5 Fault...
Page 103: ...614 00789 03...