IB140015EN
For more information visit: www.Eaton.com
Instructional Booklet
Effective: August 2014
Page
23
ATC-900 Magnum Tranfer Switch O & M Manual
Figure 26. Switching Device Closing Precautions (Closed Transition Only).
Follow Manual Operation Instructions Below
switching devices simultaneously
can cause severe injury
Attempting to close both
or death.
WARNING
2. Open both switching devices
Manual Operation Instructions
4. Verify source availability
5. Close switching device on available
source
1. Disconnect Logic Connectors
3. Verify "OPEN" flags
7805C60H05
MANUAL CLOSE BUTTON
Operating Instructions
Do Not Use Without
Reading Manual
OVERLAPPING CONTACTS
must be Synchronized
SOURCE 1 AND SOURCE 2
WARNING
7805C60H04
THIS PRODUCT CONTAINS A SPECIAL CON-
TACT ARRANGEMENT (OVERLAPPING CON-
TACTS). MISUSE CAN RESULT IN DEATH
SEVERE PERSONAL INJURY OR PROPERTY
DAMAGE.
(THIS LABEL IS APPLIED TO THE DOOR )
FOLLOW THE INSTRUCTIONS
OUTLINED IN THE NEXT
WARNING LABEL.
(THIS LABEL IS APPLIED TO
THE COVER OF THE MANUAL
CLOSE BUTTON ON EACH
THESE INSTRUCTIONS ONLY PERTAIN TO
MANUALLY CLOSING A SINGLE SWITCHING
DEVICE. ATTEMPTING TO CLOSE BOTH
SWITCHING DEVICES CAN CAUSE SEVERE
INJURY OR DEATH.
THIS LABEL IS APPLIED TO THE DOOR.