CLEARING FAILURE CODES:

  A battery failure (LED two blink red) can be cleared by 

replacing the battery. Disconnecting the battery and AC 

power, or performing a full 90 minute discharge, will 

reset the error code, however, it will return if the battery 

is faulty.

  Charge Circuit (LED three blink red) and lamp/LED 

failure (LED four blink red) will clear when the unit suc-

cessfully passes a manual or automatic 30 second test.

INDICATORS:

  LED Off - No power to unit, emergency mode.

  LED Steady Green - Unit is fully charged and is 

 oat 

charging the battery to maintain readiness.

  LED Green Pulse - Unit is in a 24 hour fast charge of 

the battery.

  LED Two Blink Red - Battery has failed a capacity test, 

or the battery is disconnected. See “Clearing Failure 

Codes” above.

  LED Three Blink Red - Battery charge circuit has failed. 

See “Clearing Failure Codes” above.

  LED Four Blink Red - Lamps have burned out, or on 

an EXIT/Combo, 50% or more of the LEDs have failed. 

See “Clearing Failure Codes” above.

  LED Steady Yellow - 30 second test or 10 second quick 

test (Fast Charge only).

  LED Blinking Yellow - 90 minute test

MAINTENANCE:

None required. Replace the batteries as needed according 

to ambient conditions. Equipment should be tested every 

30 days in accordance with local codes.

NOTE:

 Servicing of any parts should be performed by quali-

 ed personnel. Only use replacement parts supplied by Ea-

ton Lighting. Use of unauthorized parts may void the warranty.

CAUTION:

 This equipment is furnished with a sophisticated 

low voltage battery dropout circuit to protect the battery 

from over discharge after its useful output has been used. 

Allow 24 hours recharge time after installation or power 

failure prior to 90 minute testing.

TROUBLE SHOOTING GUIDE

If LED heads or charge indicator LED does not illuminate, 

check the following:

1.  Check AC supply – verify that unit has 24 hour AC 

supply.

2.  Unit is shorted or battery is not connected.

3.  Battery discharged. Permit unit to charge for 24 hours 

and then re-test.

4.  If following the above trouble shooting hints does not 

solve your problem, contact your local Eaton Light rep-

resentative for assistance

JMP12

JMP11

JMP10

JMP9

JMP8

JMP7

JMP6

JMP5

JMP4

BATT

LAMPS

N

c

TDI

ICSP

277

JMP13

JMP14

LED/SW

D5

C6

C7

C8

C9

CN4

F1

J1

JK

1

LED1

MOV1

MOV2

PR1

Q1

Q5

R7

R10

R1

3

R15

R18

R30

SW1

120

CN5

+

+

WHITE LEAD - TO NEUTRAL

BLACK LEAD - TO 120V

ORANGE LEAD - TO 277V 

CHARGER/DRIVER PCB

BATTERY

LED HEADS

OFF - EMERGENCY

MODE / POWEROFF

2 BLINK RED -

BATTERY FAILURE

STEADY GREEN -

FULL / FLOAT

CHARGE

STEADY BLINK YELLOW

- 90 MINUTE TEST

3 BLINK RED - CHARGE

 

CIRCUIT FAILURE

4 BLINK RED - LAMP/

LED FAILURE

STEADY YELLOW -

QUICK TEST

STEADY BLINK

GREEN - FAST  

CHARGE

SURE-LITES

TIME DELAY 

JUMPER

Summary of Contents for AtLite Sure-Lites SELDWA29SD

Page 1: ...where the emergency light is to be installed 2 Open the emergency light by inserting a flat screw driver in the two slots on the side of the unit then turning to separate housing from the backplate 3 To mount to a junction box Knock out drill out the appropriate mounting pattern and the wire pass hole in the back plate and the back gasket to fit the J box being used 4 To mount to conduit Unscrew the...

Page 2: ...nd Installation test Press and release the test button once during fast charge blinking green to initiate a 10 second quick test The sign will switch to emergency mode for 10 seconds allowing the installer to verify proper installation of the unit and the LED indicator will turn solid yellow 30 Second Test Press and release the test button once during float charge steady green The indica tor LED wi...

Page 3: ...h local codes NOTE Servicing of any parts should be performed by quali fied personnel Only use replacement parts supplied by Ea ton Lighting Use of unauthorized parts may void the warranty CAUTION This equipment is furnished with a sophisticated low voltage battery dropout circuit to protect the battery from over discharge after its useful output has been used Allow 24 hours recharge time after ins...

Page 4: ...aton 1121 Highway 74 South Peachtree City GA 30269 eaton com lighting 2015 Eaton All Rights Reserved Printed in USA Eaton is a registered trademark All trademarks are property of their respective owners ...

Reviews: