CLEARING FAILURE CODES:
•
A battery failure (LED two blink red) can be cleared by
replacing the battery. Disconnecting the battery and AC
power, or performing a full 90 minute discharge, will
reset the error code, however, it will return if the battery
is faulty.
•
Charge Circuit (LED three blink red) and lamp/LED
failure (LED four blink red) will clear when the unit suc-
cessfully passes a manual or automatic 30 second test.
INDICATORS:
•
LED Off - No power to unit, emergency mode.
•
LED Steady Green - Unit is fully charged and is
fl
oat
charging the battery to maintain readiness.
•
LED Green Pulse - Unit is in a 24 hour fast charge of
the battery.
•
LED Two Blink Red - Battery has failed a capacity test,
or the battery is disconnected. See “Clearing Failure
Codes” above.
•
LED Three Blink Red - Battery charge circuit has failed.
See “Clearing Failure Codes” above.
•
LED Four Blink Red - Lamps have burned out, or on
an EXIT/Combo, 50% or more of the LEDs have failed.
See “Clearing Failure Codes” above.
•
LED Steady Yellow - 30 second test or 10 second quick
test (Fast Charge only).
•
LED Blinking Yellow - 90 minute test
MAINTENANCE:
None required. Replace the batteries as needed according
to ambient conditions. Equipment should be tested every
30 days in accordance with local codes.
NOTE:
Servicing of any parts should be performed by quali-
fi
ed personnel. Only use replacement parts supplied by Ea-
ton Lighting. Use of unauthorized parts may void the warranty.
CAUTION:
This equipment is furnished with a sophisticated
low voltage battery dropout circuit to protect the battery
from over discharge after its useful output has been used.
Allow 24 hours recharge time after installation or power
failure prior to 90 minute testing.
TROUBLE SHOOTING GUIDE
If LED heads or charge indicator LED does not illuminate,
check the following:
1. Check AC supply – verify that unit has 24 hour AC
supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours
and then re-test.
4. If following the above trouble shooting hints does not
solve your problem, contact your local Eaton Light rep-
resentative for assistance
JMP12
JMP11
JMP10
JMP9
JMP8
JMP7
JMP6
JMP5
JMP4
BATT
LAMPS
N
c
TDI
ICSP
277
JMP13
JMP14
LED/SW
D5
C6
C7
C8
C9
CN4
F1
J1
JK
1
LED1
MOV1
MOV2
PR1
Q1
Q5
R7
R10
R1
3
R15
R18
R30
SW1
120
CN5
+
+
WHITE LEAD - TO NEUTRAL
BLACK LEAD - TO 120V
ORANGE LEAD - TO 277V
CHARGER/DRIVER PCB
BATTERY
LED HEADS
OFF - EMERGENCY
MODE / POWEROFF
2 BLINK RED -
BATTERY FAILURE
STEADY GREEN -
FULL / FLOAT
CHARGE
STEADY BLINK YELLOW
- 90 MINUTE TEST
3 BLINK RED - CHARGE
CIRCUIT FAILURE
4 BLINK RED - LAMP/
LED FAILURE
STEADY YELLOW -
QUICK TEST
STEADY BLINK
GREEN - FAST
CHARGE
SURE-LITES
TIME DELAY
JUMPER