5.9 TOC (Truck Operated Contacts) OPERATOR
The TOC switch, located on the right side of the cubicle, is operated
by the breaker truck frame. If the breaker is fully racked into the
cell, the truck frame operates the paddle of the TOC switch. The
TOC switch contains contacts which are used to interlock the
circuit breaker with other external devices and provide remote
indication of breaker position.
5.10 STATIC GROUNDING CONTACT
The grounding contact is an assembly of spring loaded fingers
located at the right rear of the breaker frame. The contact engages
the switchgear cell grounding bus when the breaker is pushed into
the disconnect position and maintains the breaker frame at ground
potential throughout vertical travel.
Figure 5-8 TOC Operator
Figure 5-9 Static Grounding Contact