For more information visit: www.EatonElectrical.com
Instructions for VR-Series
Replacement Breakers for
Westinghouse Type B20B/B22B
IB01301018E
I.B. 94A1994R01
Page 36
Effective: April 2005
SYMPTOM
INSPECTION AREA
PROBABLE DEFECTS
FAILS TO CLOSE
• No Trip Sound
• Control Circuit
• Control Power
(Fuse blown or switch off)
• Secondary Disconnects
• Auxiliary Switch
(a contact not making poor
or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(poor or burned or open)
• Trip Mechanism
• Trip Clapper
(Jammed)
• Trip Sound
• Trip Mechanism
• Trip Bar, Trip Latch
But no Trip
(Jammed)
• Pole Shaft
(Jammed)
• Operating Rod Assembly
(Broken or pins out)
• Vacuum Interrupter
(One or more Welded)
UNDESIRABLY TRIPS
• Control Circuit
• Control Power
(CS/T Switch, remains made)
• Mechanism
• Trip Coil Clapper
(Not resetting)
• Trip Bar or Trip Latch
(Poor engagement of mating or
worm surfaces)
• Trip Bar Reset Sprint
(Loss of torque)