Call points BG/pB Ex E VErsions
TM244 May 2019 www.eaton.com
Call points BG/PB Ex e Versions
English
BGE General arrangement
120 2
92 1
FIXING CENTRES
16 1
16 1
1 2 3
OPTIONAL
LIFT FLAP
CAPTIVE SCREW
CERT LABEL
67 2
25 1
GLAND
CENTRES
75 2
126
2
72
1
FIXING CENTRES
4 5 6
FIXING HOLES: 6.0 (4 POSITIONS)
ALL DIMENSIONS ARE IN MILLIMETERS
BGE units - operation
The unit is operated by the breaking of the glass . The
operator is protected from the broken glass by the
vinyl glass label .
Replacement of the glass
To replace the glass after operation of the unit, remove
the small outer cover held in place by the two off
slotted screws . Take out the glass and remove any
broken fragments from the unit . Place the new glass
element into the unit and replace the cover, ensuring
the 2 off slotted screws are tightened evenly . Following
replacement of the glass it is advised that the unit is
tested using the procedure outlined below .
Testing the unit
Using the test key provided, insert the key into the
test hole (situated on bottom right hand side of the
glass cover) and engage into test cam . Turn the key
in a clockwise direction (approximately 60°) . This will
simulate the breaking of the glass . Release the key to
reset the callpoint .
Ntee:
N
MEDC DO NOT recommend forcing the test key
further than 80° clockwise or 0° anti-clockwise as
this may lead to premature failure of the test cam .