6
Technical Data
MN019001EN
Effective November 2015
Bussmann series
PV Combiner box
EATON
www.eaton.com
The PV combiner box
Eaton has introduced a new line of monitored combiner boxes
designed for use with all module and inverter combinations.
Combiner box features include:
•
Designed and tested to the requirements of IEC 61439-1 and 2.
•
Compact, low-cost and highly flexible design.
•
Easy to connect input and output cabling via MC4 connectors or
IP65 rated glands.
•
Available in IP65 rated fibre-glass reinforced polyester (GRP),
IP65 powder-coated galvanised steel enclosures and IP65 rated
stainless steel in a range of sizes.
•
Internals are “touch safe” to IP20.
•
Design options include integrated load disconnects, monitoring
solutions, surge protection devices, self-powered or externally
powered solutions and wireless communication.
•
External wired modbus connection port.
Product description
For specific details regarding your combiner box design, please
see the documentation included in your order. This should provide
a detailed assembly layout and wiring diagram.
The product description is demonstrated through the Part Number
Breakdown and Rating Plate. Please ensure that careful attention
is paid to the information that is represented on the rating plate to
ensure that you are aware of the specifications of your individual
combiner box design.
Standard configurable products
Part numbers for projects outside the standard configurable prod-
ucts will be determined by an individual project part number.
Cenn-xxAyypsh-vmm
Product series = C (combiner box)
Enclosure type (e):
G =
GRP
T =
GRP with transparent polycarbonate window
M =
Painted steel enclosure
S =
Stainless steel
Number of strings (nn):
Any number of strings, 01, 02 ... 12, 13 etc. maximum 24 strings
Fuse current rating (xxA):
01A, 02A, 03A, 04A, 05A, 06A, 08A, 10A, 12A, 15A, 20A, 25A, 32A
System voltage (yy):
06 =
600 VDC
08 =
800 VDC
10 =
1,000 VDC
12 =
1,200 VDC
15 =
1,500 VDC
String protection type (p) Indicated fuse holders:
P =
Positive only fuse protection
N =
Negative only fuse protection
B =
Both positive and negative fuse protection
String protection type (p) Non-indicating fuse holders:
Q =
Positive only fuse protection
M =
Negative only fuse protection
C =
Both positive & negative fuse protection
Switch disconnect (s):
D =
Disconnect switch
F =
Fixed, no disconnect switch
Cenn-xxAyypsh-vmm
PV string input / output connection type (h)
G =
Bottom entry glands / standard output glands
M =
Bottom entry MC4s / standard output glands
S =
Left and right side entry glands / standard output glands
T =
Left and right side entry MC4s / standard output glands
U =
Bottom entry glands / armoured output glands
W =
Bottom entry MC4s / armoured output glands
X =
Left and right side entry glands / armoured output glands
Y =
Left and right side entry MC4s / armoured output glands
Over voltage protection (SPD) (v):
A =
No SPD
B =
T1 PV SPD
C =
T2 PV SPD
D =
T2 PV SPD with remote
E =
T1 PV SPD + T2 TN 240VAC SPD with remote*
F =
T1 PV SPD + T2 TT 240VAC SPD with remote*
G =
T1 PV SPD + T2 TN 240VAC SPD with
C2/D1 modbus SPD*
H =
T1 PV SPD + T2 TT 240VAC SPD with
C2/D1 modbus SPD*
J =
T1 PV SPD + C2/D1 modbus SPD*
K =
T2 PV SPD with T2 TN 240VAC SPD with remote*
L =
T2 PV SPD with T2 TT 240VAC SPD with remote*
M =
T2 PV SPD with T2 TN 240VAC SPD with C2/D1
modbus SPD*
N =
T2 PV SPD with T2 TT 240VAC SPD with C2/D1
Modbus SPD*
*P =
T2 PV SPD with C2/D1 modbus SPD*
Q =
T1/T2 PV SPD
R =
T1/T2 PV SPD with remote *
S =
T1/T2 PV SPD with T2 TN 240VAC SPD with remote *
T =
T1/T2 PV SPD with T2 TT 240VAC SPD with remote *
U =
T1/T2 PV SPD with T2 TN 240VAC SPD with C2/D1
Modbus SPD *
V =
T1/T2 PV SPD with T2 TT 240VAC SPD with C2/D1
Modbus SPD *
W =
T1/T2 PV SPD with C2/D1 Modbus SPD *
Monitoring system (mm):
M1 =
Shunt monitoring unit with 240VAC power supply – wired modbus
M2 =
Shunt monitoring unit with no power supply – wired modbus
M3 =
Shunt monitoring unit with PV power (self powered) – with modbus
Z1 =
Shunt monitoring unit with 240VAC power supply – wireless zigbee
Z2 =
Shunt monitoring unit with no power supply – wireless Zigbee
Z3 =
Shunt monitoring unit with PV power (self powered) – wireless zigbee
W1 =
Shunt monitoring unit with 240VAC power supply – industrial wireless
(EL-245U-E-A-EU)
W2 =
Shunt monitoring unit with no power supply – industrial wireless
(EL-245U-E-A-EU)
W3 =
Shunt monitoring unit with PV power (self powered) – industrial wire-
less (EL-245U-E-A-EU)