Instruction.Leaflet.

IL 29C401J

Effective December 2010

Installation Instructions for Series C F-Frame

Motor Circuit Protector Type HMCP & HMCPS

EATON CORPORATION www.eaton.com

TABLE 3-2:  SPECIAL APPLICATION MCP TRIP SETTINGS

Cam 
Setting

Continuous
Ampere
Rating

MCP
Catalog
Number

MCP 
Trip
Setting 

A

25A

HMCP025D0

40

B

43

C

46

D

49

E

52

F

55

G

58

H

60

A

50A

HMCP050G2

81

B

87

C

93

D

98

E

103

F

109

G

115

H

120

A

70A

HMCP070J2

114

B

122

C

130

D

139

E

145

F

153

G

160

H

168

A

100A

HMCP100L3

163

B

174

C

185

D

196

E

207

F

218

G

229

H

240

Motor FLA ranges are typical.  The corresponding trip setting is 

13 times the FLA value shown.  The + 20% trip tolerance can af-

fect trip response and require increase in cam setting per para 3-2.

For dc applications, actual trip levels may exceed the values 

shown by as much as 100%.  Actual dc trip values are application 

dependent.

Settings above 130 amps are for special applications.  N.E.C. 

Article 430-110(a) requires the ampere rating of the disconnecting 

means to be not less than 115% of the motor full ampere rating.

4.  INSPECTION AND FIELD CHECKS  

Series C molded case MCPs are designed to provide years of 

almost maintenance-free operation.  The following procedure 

describes how to inspect and test a MCP in service.

Inspection

MCPs in service should be inspected periodically.  The inspec-

tion should include the following checks.

BEFORE INSPECTING THE MCP IN AN ELECTRICAL 

SYSTEM, MAKE SURE THE MCP IS SWITCHED TO 

THE OFF POSITION AND THAT THERE IS NO VOLT-

AGE PRESENT WHERE WORK IS TO BE PERFORMED.  

THE VOLTAGES IN ENERGIZED EQUIPMENT CAN 

CAUSE DEATH OR SEVERE PERSONAL INJURY.

CAUTION 

MAKE SURE THAT CLEANING AGENTS OR SOLVENTS 

USED TO CLEAN THE MCP ARE SUITABLE FOR THE 

JOB.  SOME COMMERCIAL CLEANING AGENTS WILL 

DAMAGE THE NAMEPLATES OR MOLDED PARTS.

4-1.

 

Remove dust, dirt, soot, grease, or moisture from the 

 

surface of the MCP using a lint-free dry cloth, brush,

 

or vacuum cleaner.  Do not blow debris into MCP.  If

 

contamination is found, look for the source and 

 

eliminate the problem.

4-2. 

Switch MCP to ON and OFF several times to be sure

 

that the mechanical linkages are free and do not bind.  

 

If mechanical linkages are not free, replace MCP.

4-3. 

Press the PUSH-TO-TRIP button to mechanically trip

 

the MCP.  Trip, reset, and switch MCP ON several    

 

times.  If mechanism does not reset each time the MCP

 

is tripped, replace the MCP.

4-4.    Check base, cover, and operating handle for cracks, 

 

chipping, and discoloration.  MCPs should be replaced

 

if cracks or severe discoloration is found.

Summary of Contents for C Series

Page 1: ...Installation 3 Manual Operation 4 Inspection and Field Checks 6 Effective December 2010 Supersedes IL 29C401I Dated 09 09 Instruction Leaflet IL 29C401J Installation Instructions for Series C F Frame...

Page 2: ...le in 3 pole frames only The MCP is designed to comply with the applicable requirements of Underwriters Laboratories Inc Stan dard UL489 and the International Electrotechnical Commission Recommendatio...

Page 3: ...the MCP for completeness and damage before mounting BEFORE MOUNTING THE MCP IN AN ELECTRICAL SYSTEM MAKE SURE THE MCP IS SWITCHED TO THE OFF POSITION AND THAT THERE IS NO VOLTAGE PRESENT WHERE WORK IS...

Page 4: ...FF On the sliding handle barrier ON OFF and TRIP are also shown by a color coded strip for each MCP handle position red for ON white for TRIPPED and green for OFF On the sliding handle barrier ON OFF...

Page 5: ...50 D 13 8 16 0 180 E 16 1 18 3 210 F 18 4 20 6 240 G 20 7 22 9 270 H 23 0 25 2 300 A 11 5 15 2 2 50 HMCP050K2 OR HMCPS050K2 150 B 15 3 19 1 200 C 19 2 22 9 250 D 23 0 26 8 300 E 26 9 30 6 350 F 30 7 3...

Page 6: ...aintenance free operation The following procedure describes how to inspect and test a MCP in service Inspection MCPs in service should be inspected periodically The inspec tion should include the foll...

Page 7: ...ence of overheating or looseness do not disturb or tighten the connections If there is evidence of overheating terminations should be cleaned or replaced Before re energizing the MCP all terminations...

Page 8: ...ely for information purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representative The sale of the product shown in...

Reviews: