UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
S
P-164000563 Rev 1
www.eaton.com/powerquality
3-12
Table 3‐10. Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-300/300
Eaton 9395P-300/275
Eaton 9395P-300/250
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2
3
AC Input to Bypass and Output
(A, B, C, Ground)
4
2
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
1
Eaton 9395P-300/225
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2
3
AC Input to Bypass and Output
(A, B, C, Ground)
4
2
2
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
1
Eaton 9395P-300/200
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2
2
AC Input to Bypass and Output
(A, B, C, Ground)
4
2
2
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
1
All models
DC
(Separate
Battery - per
UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE 1
Bypass conduit data is not applicable to IOM configurations.
Battery Cable Routing:
Refer to the notes at the bottom of Table 3‐4 Input/Output Ratings and External Wiring Requirements.
External overcurrent protection and disconnect are not provided by this product, but
are required by codes. Refer to Table 3‐4 and Table 3‐5 for wiring requirements. If an
output lockable disconnect is required, it is to be supplied by the customer.
Table 3‐11 lists the recommended rating for input circuit breakers.
Table 3‐11. Recommended Input Circuit Breaker Ratings
UPS Model
Input Rating
Load Rating
480V
Eaton 9395P-300/300
Eaton 9395P-300/275
100% Rated
450A
Eaton 9395P-300/250
100% Rated
400A
Eaton 9395P-300/225
100% Rated
350A
Eaton 9395P-300/200
100% Rated
300A