UPS OPERATING INSTRUCTIONS
Eaton
Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
S
P-164000563 Rev 1
www.eaton.com/powerquality
7-4
A
The
UPS status
area automatically displays the Eaton model number, current time and date, active alarms,
active notices, and load percent and battery run time for the UPS. If the Eaton Environmental Monitoring Probe
is installed, the temperature and humidity sensed by the probe will also be displayed. The small head symbol
between the system model and time allows the operator select a different language from an imbedded list.
The top line of the display blinks while scrolling when the system needs attention. Some notices and alarms
may be accompanied by an audible horn. To silence the horn, touch anywhere on the control panel once
.
For
more information about alarms and notices, see paragraph 7.3.12.
B
The
information area
contains data about UPS status and operations.
C
After touching the padlock in the upper right corner, the numerical keypad appears to allow entry of the system
access pass code for operation. See Table 7‐2 Security Levels and Functions.
A
B
C
ENTER
BUTTON
Number
indicates
security
level 0 - 4
Figure 7‐4. Sign In or Password Request Screen
Table 7‐2. Security Levels and Functions
Level
Name
Passcode
Description
0
USER
NONE
USER
1
CONTROL
1111
USER + CONTROL
2
CONFIGURATION
0101
USER + C CONFIGURATION
3
SERVICE
Service
Only
USER + C CONFIGU SERVICE