Chapter 10
Product Specifications
10.1
Model Numbers
The UPS is housed in one or two free‐standing cabinets with safety shields behind
the door and front panels. The UPS is available in 50 or 60 Hz with various output
power ratings.
Models
Power Rating
Frequency
Eaton 9395P-300/300 (one or two UPM)
300 kVA, 300 kW
50/60 Hz
Eaton 9395P-300/275 (one or two UPM)
275 kVA, 275 kW
50/60 Hz
Eaton 9395P-300/250 (one or two UPM)
250 kVA, 250 kW
50/60 Hz
Eaton 9395P-300/225 (one or two UPM)
225 kVA, 225 kW
50/60 Hz
Eaton 9395P-300/200 (one or two UPM)
200 kVA, 200 kW
50/60 Hz
10.2
Specifications
The following sections detail the input, output, environmental, and battery
specifications for the UPS.
10.2.1
UPS Input
Operating Input Voltage
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
Reduced for Generator
Adjustable
Input Current Harmonic Content
3% THD at full load
Power Factor
Minimum 0.99 at full load
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc