UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
S
P-164000563 Rev 1
www.eaton.com/powerquality
3-3
Table 3‐2. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18
”
) minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36
”
) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
152.4 mm (6
”
) working space
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
S
40°C (32–104°F) at elevations up to 1000m without derating
S
For 300 kW: 0 to 35°C at elevations up to 1000m without derating.
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
95%, non-condensing
NOTE
Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental
requirements supersede the UPS requirements. Operating temperatures above the recommended range will
result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to
Eaton's Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price
Book for more information. These documents can be found at www.eaton.com/powerquality or contact an
Eaton service representative for information on how to obtain copies.
The UPS ventilation requirements are shown in Table 3‐3.
Table 3‐3. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-300/300
(CSS or IOM)
300 kVA
300 kW
480/480
11.5.(39.4)
Approximately 1180 liter/sec (2500 CFM)
With field installed UPM:
Approximately 2124 liter/sec (4500 CFM)
Eaton 9395P-300/275
(CSS or IOM)
275 kVA
275 kW
480/480
10.6 (36.1)
Eaton 9395P-300/250
(CSS or IOM)
250 kVA
250 kW
480/480
9.3 (31.9)
Eaton 9395P-300/225
(CSS or IOM)
225 kVA
225 kW
480/480
7.9 (27.0)
Eaton 9395P-300/200
(CSS or IOM)
200 kVA
200 kW
480/480
7.0 (24.0)
NOTE
CSS = Continuous Static Switch; IOM = Input Output Module
The following figures show the dimensions of the Eaton 9395P 300 kVA/kW UPS and
UPM configurations:
S
SINGLE UPM: 300 kVA/kW UPS ISBM with 1 Factory Installed UPM
(see Figure 3‐1)
S
TWO UPM: 300 kVA/kW UPS ISBM with 2 Factory Installed UPMs
(see Figure 3‐2)
S
PLUS 1: 300 kVA/kW UPS ISBM with 1 Factory Installed UPM + 1 FI-UPM
(see Figure 3‐3)