Title
Callisto 5PX G2 Service Manual
Checked
:
Rev:
Approved
:
Confidential
Page 46 of 60
This specification is the property of Eaton Corp. and shall not be reproduced or copied or used as the basis for manufacture or sale of apparatus without permission
Fault 607/60D
, Battery Fault/ No Battery
Start
End
Check battery Volt
UPS&EBM
Y
End
End
Replace UPS
Check battery wires and cables
N
No battery?
End
N
Y
Replace Battery
N
Battery Fault
?
N
Y
Battery Fault?
N
Connect them
Check CNTL?
Replace CNTL PCBA
N
Replace PSDR PCBA
Battery Fault?
End
N
Y
CNTL
PSDR
Y
Y
DC fuse is OK?
N
Battery Fault?
End
N
Y
Replae fuse
Y
PSDR
Battery detection circuit?
Change damaged
components
Battery Fault?
End
N
N
Charger output Volt?
Change charger module
Battery Fault?
Y
N
End
N
Y
Y
Y
Y