5 Failure analysis
5.1 Alarms
Code
Message
Description
0x004
UPS Temp. High
Ambient or NTC temperature is high
0x110
Building alarm
Building alarm
0x604
Battery low
Battery level is below Remaining Capacity Limit threshold or Run
Time to Empty is below Remaining Time Limit threshold.
0x802
Imminent shutoff
shut down imminent
0x806
Emergency Off
emergency stop was proceed
0x808
Overload alarm
The load percent is > the overload level setting(default 105%)
0xB01
End battery life
LCM alarm is active because timer expired
5.2 Fault
Code
Message
Description
Diagnose
0x002
Internal fault
UPS Internal fault: Main relay abnormal, NTC abnormal, or
Safety relay is failure.
Please refer below flow
chart:
0x004
UPS Temp. High
UPS internal temperature is high, over fault point
Please refer below flow
chart:
0x007
Fan Lock
Ventilator fault
Please refer below flow
chart:
0x105
AVR Too Hot
AVR is abnormal
Please refer below flow
chart:
0x107
Site Wiring Fault
Site wiring fault that can come of Phase neutral inversion on
single phase UPS
Please refer below flow
chart:
0x500
Charger Fault
Charger internal failure
Please refer below flow
chart:
0x502
Charger Too
High
The charger voltage is>2.5VPC
Please refer below flow
chart:
0x503
Charger Too Low
The charger voltage is<1.5VPC
Please refer below flow
chart:
0x607
Battery Fault
Battery need replacement OR is faulty
Please refer below flow
chart:
0x60D
No Battery
Battery not present
Please refer below flow
chart:
0x804
Imbalance Load
Load is unbalance
Please refer below flow
chart:
0x805
Short Circuit
Short circuit on output
Please refer below flow
chart: