Fault 500/Fault 502/Fault 503
, Charger Fault/
Charger Too High/ Charger
Too Low
Start
PSDR
End
Over
Replace UPS
Check whether charger output
voltage is right?
Charger Fault?
N
Check CNTL?
Replace CNTL PCBA
N
Replace PSDR PCBA
End
CNTL
Y
Charger Fault?
Check ABM Circuit is damaged?
Change charger module
N
Y
Replace damaged
components
End
N
Y
Y
Check and repair
charger circuit
N
Charger Fault?
End
N
Y
Charger Fault?
N
Y